INSP-Final Inspection | 9/12/2008 | 9/12/2008 | 9/12/2008 | A | PASS |
Forrest France
|
|
|
Necessary corrections are finished, fire sprinkler permit finaled.
|
INSP-Final Inspection | 9/10/2008 | 9/11/2008 | 9/11/2008 | A | FAIL |
Forrest France
|
|
|
Added heads below the ductwork need to match response type within the same fire area.
|
INSP-Final Inspection | 9/8/2008 | 9/9/2008 | 9/9/2008 | P | FAIL |
Forrest France
|
|
|
Upright heads at one branch line do not meet obstruction tables per NFPA 13 8.6.5.1.2 due to adjacent ductwork.
|
INSP-Sprinkler Rough-in/Hydro | 8/5/2008 | 8/6/2008 | 8/6/2008 | A | PART |
Forrest France
|
|
|
OH fire sprinkler modifications are acceptable, grid ceiling and pendent heads are not yet installed at the west side, plans do not reflect actual wall layout-however spacing and locations are okay.
|