Miscellaneous action | | | 3/11/2009 | | DONE |
|
|
|
Sent for archiving
|
INSP-Final Inspection | 12/19/2008 | 12/19/2008 | 12/19/2008 | P | PASS |
Forrest France
|
|
|
C/N items verified for completion, fire sprinkler permit finaled.
|
INSP-Sprinkler Rough-in/Hydro | 12/16/2008 | 12/16/2008 | 12/16/2008 | P | FAIL |
Forrest France
|
|
|
Two heads at a meeting room need relocated, one head at a storage room is overspaced, annotated areas on plans approved for cover with today's date.
|
INSP-Sprinkler Rough-in | 12/2/2008 | 12/3/2008 | 12/3/2008 | P | PART |
Forrest France
|
|
|
Okay to cover pendent heads at the new entry vestibule, one additional pendent at the reception area soffit also okayed.
|
INSP-Sprinkler Rough-in | 11/18/2008 | 11/18/2008 | 11/18/2008 | A | PART |
Forrest France
|
|
|
Site verified relocated head at an exam room and one additional head installed at the common corridor vestibule per plans.
|
INSP-Final Inspection | 11/14/2008 | 11/17/2008 | 11/17/2008 | P | PART |
Forrest France
|
|
|
Noted correction items finished.
|
INSP-Final Inspection | 11/13/2008 | 11/14/2008 | 11/14/2008 | A | FAIL |
Forrest France
|
|
|
Noted obstructed pendent head at exam room 124, missing one head to be added per approved drawings at the hallway vestibule, see locations annotated on stamped plan set.
|
INSP-Sprinkler Rough-in | 11/7/2008 | 11/10/2008 | 11/10/2008 | P | PASS |
Troy Cobbley
|
|
|
See the city approved plans for locations where the sprinkler piping can be covered. It will have todays date and my signature.
|
INSP-Sprinkler Rough-in/Hydro | 10/28/2008 | 10/28/2008 | 10/28/2008 | A | PART |
Forrest France
|
|
|
OH system modifications approved as noted on plans to date.
|
INSP-Sprinkler Rough-in | 10/24/2008 | 10/24/2008 | 10/24/2008 | P | PART |
Forrest France
|
|
|
See city approved plans for areas OK to cover. KR
|
INSP-Final Inspection | 9/25/2008 | 9/25/2008 | 9/25/2008 | P | PART |
Forrest France
|
|
|
OH rough-in for the "sleers" area only completed today, circled locations on plans approved for cover, noted one head at the reception counter soffit to be added per drawings, flex-head resubmittals verified.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 9/25/2008 | | DONE |
Cathy Brown
|
|
|
|
Inspection Record Card- Fire | 9/25/2008 | | 9/25/2008 | | DONE |
Cathy Brown
|
|
|
|
Telephone call | | | 9/25/2008 | | DONE |
Cathy Brown
|
|
|
tlk to jeff already this morning about the permit and fees 8:00 am
|
Permit Ready to Issue | | | 9/25/2008 | | DONE |
Cathy Brown
|
|
|
|
CHANGE STATUS TO (ISS) | | | 9/25/2008 | | DONE |
Alexandra L. DeYoung
|
|
|
|
Plan assigned to (OutSourced) | 9/24/2008 | | 9/24/2008 | | DONE |
Cathy Brown
|
|
|
|
Sprinkler Plan Check | 9/16/2008 | | 9/23/2008 | | PASS |
|
|
|
These plans were previously approved. This second review of the plan modification and revised calculations affected 14 heads within the remote area of operation. This modification does not appear to adversely affect the remote area of operation.
Bryan Johnson
|
Plan resubmittals received | | | 9/16/2008 | | DONE |
|
|
|
received 1 letter of transmittal, 5 applications and 5 sets of plans stamped re-submittal and put in fire box
|
INSP-Sprinkler Rough-in/Hydro | 9/11/2008 | 9/12/2008 | 9/12/2008 | A | FAIL |
Forrest France
|
|
|
Need to provide documentation addressing the installation of flex type head connections is approved. See item # 13 on the plan review for details. Overhead cover at the drop ceilings is not allowed at this time.
|
Telephone call | | | 8/14/2008 | | DONE |
|
|
|
t/c w damaris melick at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 8/14/2008 | | DONE |
|
|
|
|
Issue and Print Permit | | | 8/14/2008 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 8/13/2008 | | 8/13/2008 | | DONE |
|
|
|
|
Sprinkler Plan Check | 7/31/2008 | | 8/13/2008 | | PASS |
|
|
|
plans are approved
|
PLANS/APPL TAKEN TO FRONT DESK | | | 8/13/2008 | | DONE |
|
|
|
|
Application received | | | 7/31/2008 | | |
|
|
|
|
Pending Assignment by SAM | 7/31/2008 | | | | |
|
|
|
|
Plan assigned to (SAM) | 7/31/2008 | | | | |
|
|
|
|