Permit Information
Permit NumberFIR08-00550
StatusVoid/No Violation
Name PEAK ALARM
Site Address 5256 W FAIRVIEW AVE
Project NamePLAZA SEVEN
Customer Number 
ePlanReview 
Description
08-06-09 PLAN MODIFICATION
This plan modification is to incorporate field modifications to the record drawings. Includes increasing candela due to actual device locations, changing strobe only devices to horn/strobes where audibility requirements were not met, and revising the one-line and calculations based on the field modifications.

08-12-08:
This fire alarm permit is to replace the existing non-functioning fire alarm panel with a new one. Scope includes manual fire alarm system, HVAC & Sprinkler system monitoring (the building is only sprinklered in the basement), and elevator recall functions.
There is no associated building permit.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Permit VOIDED9/13/20189/13/20189/13/2018 DONE
DetailsBrittany Hill
Jeremy berg, they did not do the work. Lee stated to him to call in and have the permit voided
Miscellaneous action  9/10/2018 DONE
Emailed Jeremy Berg to get an update. Asked him to schedule an acceptance test if work has been completed.
FIR-Aging Inspection4/25/20184/25/20184/27/2018 NR
DetailsTroy Cobbley
This permit will need to be voided due to another contractor is taken over the work.
FIR-Aging Inspection9/25/20179/25/20179/25/2017 NR
DetailsTroy Cobbley
Waiting for fire dept. follow up and contractor to call for final inspection
FIR-Aging Inspection5/8/20175/8/20175/8/2017 NR
DetailsTroy Cobbley
Waiting on fire dept follow up
FIR-Aging Inspection10/26/201610/26/201611/1/2016 NR
DetailsTroy Cobbley
I turned this over to the fire dept for follow up
FIR-Aging Inspection7/27/20167/27/20167/27/2016 NR
DetailsTroy Cobbley
I spoke to Assistant Chief Ron Johnson about a previous request for help.
INSP-Conference3/11/20163/11/20163/11/2016PDONE
DetailsTroy Cobbley
Wendy contacted me and stated that Peak Alarm is no longer in a business arrangement with the building owner. I spoke to Scott and have forwarded information to Chief Gervais with the Fire Dept.
FIR-Aging Inspection3/7/20163/7/20163/11/2016 NR
DetailsTroy Cobbley
I left a voice message for Wendy the Office Manager requesting that the project be finished up.
INSP-Final Inspection11/7/201311/8/201311/8/2013AFAIL
DetailsTroy Cobbley
Began inspection by verifying the sync of the audio/visual devices. When testing the horns on most of the first floor and the west half of the second floor failed to work. Inspection stopped and no devices tested.
FIR-Aging Inspection10/28/201310/28/201310/29/2013 NR
DetailsTroy Cobbley
I left message for Mike requesting project status
FIR-Aging Inspection9/4/20129/4/20129/12/2012 NR
DetailsTroy Cobbley
I spoke to Jason and Mike and they were going to follow up on this project.
INSP-Final Inspection4/18/20114/20/20114/20/2011PFAIL
DetailsTroy Cobbley
Neither the strobes or the horn were syncronized. Also need to test all initiating devices. Candella needs to be modified to 110cd on the strobe in the old engineering office. End of Line voltage was verified ok as well as spacing of the manual pull stations and audio/visual devices. Netcon was also verified at 5.
FIR-Aging Inspection4/18/20114/18/20114/19/2011 NR
DetailsTroy Cobbley
wip
INSP-Final Inspection2/3/20112/4/20112/4/2011PCANC
DetailsTroy Cobbley
Per Mike madsen and my discussion this inspection will be rescheduled for next week.
FIR-Aging Inspection1/17/20111/17/20111/24/2011 NR
DetailsTroy Cobbley
wip
FIR-Aging Inspection11/15/201011/15/201011/17/2010 NR
DetailsTroy Cobbley
Mike stated that this should be set up for inspection the week after Thanksgiving.
Telephone call  5/11/2010 DONE
Peak Alarm called to let us know they haven't called for an inspection yet because they are trying to obtain an acceptable NETCON rating.
Telephone call  4/19/2010 DONE
Spoke to Mike regarding the project status. He will be calling in for a final inspection on 4/28/10.
CHANGE STATUS TO (ISS)  8/7/2009 DONE
(F) Reprint permit  8/7/2009 DONE
Alarm Plan Check8/6/2009 8/6/2009 PASS
DetailsStephanie L. Cobbley
See review comments
PLANS TAKEN FRONT DESK ALARM  8/6/2009 DONE
Approved plans and calcs available at front counter
Telephone call  8/6/2009 DONE
Details
left message w richard for rodney at ###-#### - permit (plan mod) ready and fees given
Permit Ready to Issue  8/6/2009 DONE
Details
Plan assigned to (Stephanie)7/31/2009 8/6/2009 DONE
DetailsStephanie L. Cobbley
8/6/2009 09:30:23 SLC - activity updated through activity FIRA24 from case FIR08-00550.
1st review completed  8/3/2009 DONE
Alarm Plan Check8/3/2009 8/3/2009 FAIL
DetailsStephanie L. Cobbley
Plans did not accurately reflect field modifications. I called Mary F. to explain the discrepencies. She let me know she did not recieve the correct information from the field and will resubmit as soon as possible.
Plan resubmittals received  8/3/2009  
DetailsTisha Gallop
received two copies of small documents, plan sheets FA-00, FA-22, FA-30, three copies of FA-21, one copy of FA-20; taken to fire review
Plan resubmittals received  7/31/2009  
DetailsTisha Gallop
Plan Modification: received application, submittal documents and two copies of sheets FA-00, FA-20, FA-21, FA-22, FA-30; taken to fire review
INSP-Final Inspection4/1/20094/2/20094/2/2009AFAIL
DetailsTroy Cobbley
Plans need to be resubmitted for "plan modifications". This is due to extensive audio/visual modifications required such as additional devices, relocated devices and devices that need the candella adjusted brighter. Also the second floor tenant "ABC Channell 6" has a door magnet securing the exit door. The fire alarm contractor and I spoke about minimum sound requirements in the radio transmission rooms where only strobes had been installed and for all rooms. No devices were actually tested. An EOL had to be relocated in the NAC panel so that it would report a trouble
Telephone call  3/24/2009 DONE
Left a message for Rodney at Peak Alarm asking for the status of this project.
Telephone call  3/24/2009 DONE
Rodney with Peak Alarm called to let us know he will be calling in for an inspection this week.
INSP-Conference1/12/20091/12/20091/12/2009PDONE
DetailsTroy Cobbley
I left a message for Mark Cleverly with Thornton Ovliver that we were assured on 12/8/08 the alarm system installation would proceed. I visited the job site and found the alarm system still not functional and the building occupied. I contacted Mike with Peak Alarm and he stated that they would have the PIV connected today and then they would be waiting on phone lines and the elevator. Per the elevator contractor they are atleast three week out. I told Mike that the fire alarm system needs to be up and running. He was going to contact his boss and verify when phone lines would be installed.
Telephone call  12/12/2008 DONE
telcon from David, at Mackay Eclec, requesting approval for them to install conduit for the fire alarm system under this permit. I indicated they can, if they are subcontracted with Peak alarm to do the work and the work is specifically included under the plans issued with this permit.
Telephone call  12/2/2008 DONE
Telcon today with Karen Thomas, Thorton Oliver Keller, (###-####). She indicates they were waiting for elevator upgrades to be completed, but they have been postedponed to January. She has therefore made arrangements with the fire alarm contractor to begin work installing the fire alarm system on Monday, 12/8. All components are reportedly in stock for the installation to begin.
FIR-Aging Inspection11/26/200811/26/200812/1/2008 NR
DetailsTroy Cobbley
I contacted peak alarm and they said that they would be on the job at the end of December or January as per their contact. I said "so this building has a non-functioning fire alarm system?" And they said yes.

I have forwarded this information to sam rogers and mark sentenno for further action.

Issue and Print Permit  8/27/2008 DONE
Plan assigned to (Stephanie)8/5/2008 8/12/2008 DONE
DetailsStephanie L. Cobbley
Alarm Plan Check  8/12/2008 PASS
See redlined drawings and review comments
PLANS/APPL TAKEN TO FRONT DESK  8/12/2008 DONE
Inspection Record Card- Fire8/12/2008 8/12/2008 DONE
Details
Permit Ready to Issue  8/12/2008 DONE
Details
Telephone call  8/12/2008 DONE
Details
t/c w rodney larkey at ###-#### - permit ready and fees given
Application received  8/5/2008  
Case Summary  8/5/2008 DONE