Miscellaneous action | | | 3/10/2009 | | DONE |
|
|
|
Sending for archiving
|
INSP-Final Inspection | 11/20/2008 | 11/21/2008 | 11/21/2008 | A | PASS |
Troy Cobbley
|
|
|
Foward flush completed, alarm inter- connection testing completed. KR
|
INSP-Sprinkler Rough-in | 11/6/2008 | 11/7/2008 | 11/7/2008 | A | PASS |
Troy Cobbley
|
|
|
the 24 hr air test passed
|
INSP-Sprinkler Rough-in | 11/6/2008 | 11/6/2008 | 11/7/2008 | P | PASS |
Troy Cobbley
|
|
|
The 24 hr air test was started with 41 1/14 psi on the guage.
|
INSP-Sprinkler Rough-in/Hydro | 10/16/2008 | 10/17/2008 | 10/17/2008 | A | PASS |
Troy Cobbley
|
|
|
The overhead hydro tests for both the wet and the dry systems passed.
|
INSP-Supply line flush | 10/16/2008 | 10/17/2008 | 10/17/2008 | A | PASS |
Troy Cobbley
|
|
|
Underground flush passed
|
(F) Reprint permit | | | 10/15/2008 | | DONE |
|
|
|
|
CHANGE STATUS TO (ISS) | | | 10/15/2008 | | DONE |
|
|
|
|
Sprinkler Plan Check | 10/8/2008 | | 10/14/2008 | | PASS |
|
|
|
This was the 5th review of these previously approved plans.. The plans were resubmitted due to modifications made during construction where 18 additional heads were added to the job total head count. By request, an additional set of calculations for the attic was also submitted for review. As a result 18 heads were affected in the new remote area calculation submitted. Plans are approved by Bryan Johnson
|
PLANS/APPL TAKEN TO FRONT DESK | | | 10/14/2008 | | DONE |
Cathy Brown
|
|
|
|
Inspection Record Card- Fire | 10/14/2008 | | 10/14/2008 | | DONE |
Cathy Brown
|
|
|
|
Telephone call | | | 10/14/2008 | | DONE |
Cathy Brown
|
|
|
tlk to receptionist for lily ###-#### that permit and fees are ready to be picked up
|
Permit Ready to Issue | | | 10/14/2008 | | DONE |
Cathy Brown
|
|
|
|
Plan resubmittals received | | | 10/8/2008 | | |
Sam Rogers
|
|
|
Plan Modifcation, Rec'd 5 copies of application, binder of submittal info and plan sheets FP1, FP2, anf FP3; taken to fire review
|
INSP-Sprinkler Rough-in | 10/2/2008 | 10/3/2008 | 10/3/2008 | A | PASS |
Troy Cobbley
|
|
|
The remaining sprinkler piping is ok to cover where the sprinkler coverage was inadequate due to the roof transitions. I kept one copy of the as-builts to be compared with the city approved plans when received.
|
INSP-Sprinkler Rough-in | 9/30/2008 | 9/30/2008 | 9/30/2008 | P | NR |
Troy Cobbley
|
|
|
I stopped at the job site and spoke to Ryan. This inspection was for a cover of the remaining piping. I did not give approval since the dry system piping iinstallation has been modified to provide correct protection at the roof elevation transitions; no plans for the modification were on site. This redesign effects the hydraulic calculations, siesmic calculations, volume of the dry system which could effect air compressor sizing and trip times. Approved resubmittals are required prior to cover or the contractor needs to meet with the Boise City Fire Dept. to make other arrangements for cover.
|
Plan resubmittals received | | | 9/30/2008 | | |
|
|
|
received "5" sets of plans including as app for each one- put plans on fire shelf
|
INSP-Sprinkler Rough-in | 9/24/2008 | 9/25/2008 | 9/25/2008 | A | PART |
Troy Cobbley
|
|
|
All of the outstanding rough-in issues have been taken care of except for verification from Tyco that the BB1 head installation still meets the manufacturers listing at the two areas of roof transitions. I have approved cover for all areas except for these two locations. Forrest France first addressed this issue on 9-22-2008. I let Ryan know that approved resubmittals will be required prior to a final inspection. My "redlined" city approved drawings are to be submitted to Bryan Johnson with this resubmittal. The building owner was witness to and part of the above conversations. I also found one pendant head in the west wing that was overspaced. Correct spacing will be verified at the final.
|
INSP-Sprinkler Rough-in | 9/22/2008 | 9/23/2008 | 9/23/2008 | P | FAIL |
Troy Cobbley
|
|
|
Todays inspection was for the wet system. See the city approved plans for deficienceis and there locations. See the city approved plans for the one wing that can have the piping covered since no corrections for the wet or dry system were in this area. The rest of the building has deficiencies listed in red on the city approved plans. They include overspaced heads in the kitchen area. It appears additional heads will be required since the room size exceeds the maximum spacing of the pendant heads as calculated in the room. The size of the piping on the plans does not match what has been installed which includes the corridor remote area. Many heads are closer together than the allowed 8'-0". Heads in the corrior are blocked by a beam and will not provide coverage into the "pockets". The 2" wet system main supplied directly from the riser room has been rerouted and does not match plans. Where there were three elbows, there are now alot of tees which will add to the overall friction loss. While looking at the wet system I noticed that the side sammy's are not installed the minimum distance above the bottom of the truss as required by NFPA 13. I also verified Forrest Frances concern that the 1/4" shank side sammys are being used for piping exceeding 2 1/2" in diameter which is not allowed per the web site. The fitter did not have the specific model number of the attachment used. I let Ryan know that resubmittals will be required showing all of the changes prior to a fire sprinkler final.
|
INSP-Sprinkler Rough-in/Hydro | 9/19/2008 | 9/22/2008 | 9/23/2008 | A | CANC |
Troy Cobbley
|
|
|
Could this be after 9:00am. Ryan is the contact. Thanks Phone #: ###-#### Internet Inspection Request from: Stan Beus
|
INSP-Sprinkler Rough-in/Hydro | 9/22/2008 | 9/22/2008 | 9/22/2008 | P | FAIL |
Forrest France
|
|
|
Dry system rough-in failed, items include two missing upright heads and piping not installed, 5 BB attic heads to be replaced due to field modified deflector orientation, overspaced coverage at one location above the riser room, noted remote inspectors test connection has been moved from where indicated on approved plan, also noted possible coverage issue at hatched areas due to change in roof pitch at zone of coverage for the BB heads. Also discovered two leaks to be repaired and bushings at some fittings.
|
INSP-Sprinkler Rough-in/Hydro | 9/22/2008 | 9/22/2008 | 9/22/2008 | A | PART |
Forrest France
|
|
|
Overhead dry system and wet system hydrostatic testing passed. KR
|
INSP-Sprinkler Rough-in/Hydro | 9/19/2008 | 9/19/2008 | 9/19/2008 | P | CANC |
Troy Cobbley
|
|
|
Could not make the inspection due to time constraints.
|
INSP-Sprinkler Rough-in/Hydro | 9/19/2008 | 9/22/2008 | 9/19/2008 | A | CANC |
Troy Cobbley
|
|
|
Ryan is the contact. Thanks Phone #: ###-#### Internet Inspection Request from: Stan Beus Inspection cancelled from web by: Stan Beus
|
Inspection Record Card- Fire | 9/19/2008 | | 9/19/2008 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 9/19/2008 | | DONE |
|
|
|
|
Telephone call | | | 9/19/2008 | | DONE |
|
|
|
t/c w lillie at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 9/19/2008 | | DONE |
|
|
|
|
Issue and Print Permit | | | 9/19/2008 | | |
|
|
|
|
Sprinkler Plan Check | 9/8/2008 | | 9/17/2008 | | PASS |
|
|
|
plans are approved with conditions
|
Plan resubmittals received | | | 9/8/2008 | | |
Tisha Gallop
|
|
|
Received five copies of application, binder of submittal info and plan sheets FP1, FP2, FP3; taken to fire review
|
Sprinkler Plan Check | 8/19/2008 | | 9/2/2008 | | FAIL |
|
|
|
These plans were denied due to several reasons including missing or lack of information. Upon request, the denied set of plans may be retrieved from my office for salvage. The denied set of plans will be maintained for 5 working days.
|
Sprinkler Plan Check | 8/5/2008 | | 8/19/2008 | | PEND |
|
|
|
These sprinkler plans have been put on hold while awaiting new project information from the Fire Sprinkler Contractor (Shilo). The new information is expected by the end of this week or August 22nd per conversation with the project contact person Lillie Scales.
|
Early Start | | | 8/12/2008 | | DONE |
|
|
|
Approved Early Start request (Doc atttached)
|
Application received | | | 8/5/2008 | | |
|
|
|
|
Pending Assignment by SAM | 8/5/2008 | | | | |
Sam Rogers
|
|
|
|
Pending Assignment by SAM | 9/30/2008 | | | | |
|
|
|
|
Plan assigned to (SAM) | 10/8/2008 | | | | |
|
|
|
|