Miscellaneous action | | | 5/11/2009 | | DONE |
|
|
|
Plans taken to records to scan
|
INSP-Final Inspection | 10/8/2008 | 10/9/2008 | 10/9/2008 | P | PASS |
Forrest France
|
|
|
Noted correction items field verified for compliance, fire alarm permit finaled.
|
INSP-Final Inspection | 10/2/2008 | 10/6/2008 | 10/6/2008 | A | FAIL |
Troy Cobbley
|
|
|
See the city approved plans for deficiencies that include knox box, signage on facp room door, map at annunciator, as-builts and provide a ceiling in the facp room.
|
INSP-Final Inspection | 10/1/2008 | 10/2/2008 | 10/2/2008 | A | CANC |
Forrest France
|
|
|
Scheduled by a contractor via Hello! on 10/1/2008 at 3:52:21 PM. Contact: ###-####.
|
INSP-Final Inspection | 10/1/2008 | 10/1/2008 | 10/1/2008 | P | FAIL |
Forrest France
|
|
|
Noted overspaced smoke detection, one detector to be relocated due to proximity to HVAC diffuser, need to relocate SD at the FACP, missing signage at the door to the control panel room, no testing completed at this time, see plans for annotations.
|
INSP-Final Inspection | 9/8/2008 | 9/8/2008 | 9/9/2008 | P | CANC |
Troy Cobbley
|
|
|
Wrong inspection number.
|
Issue and Print Permit | | | 8/20/2008 | | DONE |
|
|
|
|
Plan assigned to (Stephanie) | 8/7/2008 | | 8/13/2008 | | DONE |
Stephanie L. Cobbley
|
|
|
|
Alarm Plan Check | | | 8/13/2008 | | PASS |
|
|
|
See redlined drawings and review comments
|
PLANS/APPL TAKEN TO FRONT DESK | | | 8/13/2008 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 8/13/2008 | | 8/13/2008 | | DONE |
|
|
|
|
Telephone call | | | 8/13/2008 | | DONE |
|
|
|
t/c w matt casey at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 8/13/2008 | | DONE |
|
|
|
|
Case Summary | | | 8/7/2008 | | DONE |
|
|
|
|
Case Summary | | | 8/7/2008 | | DONE |
|
|
|
|
Application received | | | 8/7/2008 | | |
|
|
|
|