INSP-Final Inspection | 1/30/2009 | 1/30/2009 | 1/30/2009 | P | PASS |
Forrest France
|
|
|
Fire sprinkler permit finaled.
|
INSP-Sprinkler Rough-in/Hydro | 1/30/2009 | 1/30/2009 | 1/30/2009 | P | PASS |
Forrest France
|
|
|
Corrections field verified, inspection passed.
|
INSP-Sprinkler Rough-in/Hydro | 1/28/2009 | 1/29/2009 | 1/29/2009 | A | FAIL |
Forrest France
|
|
|
New sidewall head at the stairway landing is installed beyond the lowest dimension below the deck per head listing, added upright at the storage room does not match response type or temp. with the adjacent head in the same fire area.
|
Miscellaneous action | | | 9/5/2008 | | DONE |
|
|
|
this permit was created to track with a newly created Grape Escape TI building permit. (work previoulsy was included under the building shell permit BLD08-01464)
|
INSP-Sprinkler Rough-in | 8/28/2008 | 8/28/2008 | 8/28/2008 | A | PART |
Forrest France
|
|
|
See plan annotations for locations inspected to date.
|
INSP-Sprinkler Rough-in | 8/27/2008 | 8/27/2008 | 8/27/2008 | P | PART |
Forrest France
|
|
|
Locations on approved plan marked okayed with today's date including the restrooms and storage closet. Approved installation at the men's restroom and adjacent mech. closet only, womens restroom is not yet complete (in Grape Escape tenat space).
|
INSP-Sprinkler Rough-in/Hydro | 8/15/2008 | 8/15/2008 | 8/15/2008 | P | PART |
Troy Cobbley
|
|
|
No hydrostatic test required. One upright head found to be overspaced in Grape Escape was corrected while I waited. The high temperature upright, to be located infront of the hood, in the Pie Hole will not be installed until Monday. Per Sam Rogers, it is approved for both the restaurants to open at this time, with the commitment from the sprinkler contractor that the additional head in the Pie Hole will be installed early next week. The sprinkler work shown out side of the restraunts is not done yet. All construction work was submitted and approved under a "shell" building permit. Sprinkler rough-in piping in the newly roughed in restroom in Pie Hole wukk not provide protection above the proposed level of future ceiling. This needs to be resolved before the "final" of this sprinkler permit.
|
Pending Assignment by SAM | 8/14/2008 | | 8/15/2008 | | DONE |
Sam Rogers
|
|
|
Plan submitted as a Quick permit but falls outside the guidelines. Agreed to rush the review for Randy, at Debest. Faxed plan to B. Johnson for review this morning.
|
Sprinkler Plan Check | 8/14/2008 | | 8/15/2008 | | PASS |
|
|
|
PLANS DONE BY BRYAN JOHNSON
|
PLANS/APPL TAKEN TO FRONT DESK | | | 8/15/2008 | | DONE |
Cathy Brown
|
|
|
|
Permit Ready to Issue | | | 8/15/2008 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 8/15/2008 | | 8/15/2008 | | DONE |
Cathy Brown
|
|
|
|
Inspection Record Card- Fire | 8/15/2008 | | 8/15/2008 | | DONE |
Cathy Brown
|
|
|
|
Issue and Print Permit | | | 8/15/2008 | | DONE |
|
|
|
|
Application received | | | 8/14/2008 | | |
|
|
|
|