Miscellaneous action | | | 5/11/2009 | | DONE |
|
|
|
Plans taken to records to scan
|
INSP-Final Inspection | 3/9/2009 | 3/9/2009 | 3/9/2009 | P | PASS |
Forrest France
|
|
|
Fire alarm permit okay for finaled status.
|
INSP-Final Inspection | 1/15/2009 | 1/16/2009 | 1/16/2009 | A | PART |
Forrest France
|
|
|
Final pending installation of a knox box per review comments, remainder of system testing passed after horn circut trouble and account information repaired and adjusted.
|
INSP-Final Inspection | 12/14/2008 | 12/15/2008 | 12/15/2008 | P | DEFR |
Forrest France
|
|
|
Scheduled by a contractor via Hello! on 12/14/2008 at 10:31:12 PM. Contact: ###-####.
|
FIR-Aging Inspection | 11/21/2008 | 11/21/2008 | 11/24/2008 | | DEFR |
Forrest France
|
|
|
Work in progress
|
Inspection Record Card- Fire | 8/22/2008 | | 8/22/2008 | | DONE |
|
|
|
|
Telephone call | | | 8/22/2008 | | DONE |
|
|
|
left message w laura for charlie bayne at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 8/22/2008 | | DONE |
|
|
|
|
Issue and Print Permit | | | 8/22/2008 | | DONE |
|
|
|
|
Alarm Plan Check | | | 8/21/2008 | | PASS |
|
|
|
See redlined drawings and review comments
|
PLANS/APPL TAKEN TO FRONT DESK | | | 8/21/2008 | | DONE |
|
|
|
|
Telephone call | | | 8/21/2008 | | DONE |
|
|
|
Spoke to Chris Willis and asked for new battery calculations to add a remote annunciator panel and for the data sheet as well. He emailed them to me right away. They are included in the submittal packet.
|
Application received | | | 8/15/2008 | | |
|
|
|
|
Plan assigned to (Stephanie) | 8/15/2008 | | 8/15/2008 | | DONE |
Stephanie L. Cobbley
|
|
|
|
Case Summary | | | 8/15/2008 | | DONE |
|
|
|
|