Permit Information
Permit NumberFIR08-00595
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 1388 S ENTERTAINMENT AVE
Project NameSpectrum Resturant
Customer Number 
ePlanReview 
Description
FIR OH Scope: 10/28/08
Corrected plans and calculations have been provided. The ECHSW heads have been changed to Pendant heads. The revision is noted as Revision #3 and dated 10/15/08.
FIR OH Scope:
Beginning from an existing 6” supply, install a 4” RPZ back flow device and wet riser to serve through out the warm areas and an auxiliary anti-freeze system to serve the cold areas. The fire sprinkler system work shall comply with the IFC 2006, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD08-00896 & UG permit FIR08-00514.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  3/10/2009 DONE
Sent for archiving
INSP-Final Inspection2/9/20092/9/20092/9/2009PPASS
DetailsTroy Cobbley
permit finaled
INSP-Conference1/7/20091/7/20091/7/2009PDONE
DetailsTroy Cobbley
I spoke to Brian Johnson and to Andy, the builder, about the PIV that was shown to be installed on the overhead sprinkler plans has not been installed. Per the separate underground permit FIR08-00514 no PIV was being installed. The PIV needs to be installed, a wall PIV approved by the city of boise installed or the one hour room with exterior access provided. Brian stated that he would contact me with a solution.
INSP-Sprinkler Rough-in12/23/200812/23/200812/23/2008PFAIL
DetailsForrest France
Wrong permit number request, intended for Tenant Improvement work.
INSP-Sprinkler Rough-in11/13/200811/14/200811/14/2008APART
DetailsForrest France
Reinspection for adjusted upright head locations in the truss webs at the roof deck passed. Noted three non-sprinklered concealed spaces at the SW round- locations marked on plans- in need of coverage or meet exceptions per NFPA.
INSP-Sprinkler Rough-in11/12/200811/14/200811/13/2008ACANC
DetailsTroy Cobbley
Your contact is Richard. Thanks. Phone #: ###-#### Internet Inspection Request from: Stan Beus Inspection cancelled from web by: Stan Beus
INSP-Sprinkler Rough-in11/4/200811/5/200811/5/2008APASS
DetailsTroy Cobbley
The east exterior canopy can be covered now that the piping type and sizing has been corrected.
INSP-Sprinkler Rough-in/Hydro10/31/200811/3/200811/3/2008APASS
DetailsTroy Cobbley
Above ground hydro test passed.
INSP-Sprinkler Rough-in/Hydro10/29/200810/31/200810/31/2008ACANC
DetailsTroy Cobbley
Per Charles the hydro test is to be cancelled.
INSP-Sprinkler Rough-in10/30/200810/31/200810/31/2008APART
DetailsTroy Cobbley
The southwest canopy can be covered. The east canopy can not be covered due to cpvc piping being installed where as the plans indicate steel piping is to be installed. Plans either need to be resubmitted or piping is to be installed as per the plans. Also the upright sprinkler heads through out the rest of the building have not been installed as per NFPA 13 8.6.5.2.1.6 and exhibit 8.20. The general contractor also stated that he would install insulation in the eaves of the tower located on the southwest corner of the building. This space is considered a combustible concealed space.
INSP-Sprinkler Rough-in10/29/200810/30/200810/30/2008PNR
DetailsForrest France
PLANS/APPL TAKEN TO FRONT DESK  10/29/2008 DONE
Inspection Record Card- Fire10/29/2008 10/29/2008 DONE
DetailsCathy Brown
Issue and Print Permit  10/29/2008 DONE
Telephone call  10/29/2008 DONE
tlk to lilly that permit is ready to be picked up
Sprinkler Plan Check10/17/2008 10/28/2008 PASS
Details
Note: this was the third review of these plans. 26 heads over three remote areas of operation were affect as a result of this plan review. Plans are approved by Bryan Johnson
Plan resubmittals received  10/17/2008 DONE
Received 5 resubmittal applications, and 5 copies of sheets FPI OF 3, PP2 OF 3, FP3 OF 3 SENT TO FIRE
Miscellaneous action  10/13/2008 DONE
Troy Cobbley reported that during the underground inspection today, the overhead sprinkler piping was observed to be mostly installed; installation deficiencies were also apparent. He advised Randy Knudson that a stop work order will be posted and a double fee will apply to the permit when issued.
Sprinkler Plan Check9/23/2008 9/27/2008 FAIL
Details
These plans were denied. The plans and calculations did not correlate and the selected heads for use in the Dining Room were not listed for the application.
Upon request, the denied set of plans may be retrieved from my office for salvage. The denied set will be maintained for 5 working days.
Sprinkler Plan Check9/21/2008 9/23/2008 NR
Details
Spectrum plans are on hold pending further information from the contractor.
Plan resubmittals received  9/12/2008  
received "5" sets of plans with an application for each set. put plans on fire shelf
Sprinkler Plan Check8/21/2008 9/1/2008 FAIL
Details
These plans were denied due to a material listing discrepancy. Upon request, the denied set of plans may be retrieved from my office for salvage. The denied set will be maintained for 5 working days.
Case Summary  8/21/2008 DONE
DetailsMarsha Smylie
Application received  8/21/2008  
DetailsMarsha Smylie
Pending Assignment by SAM8/21/2008    
DetailsSam Rogers