Permit NumberFIR08-00601
StatusFinaled
Name ALARM STAR
Site Address 10681 W MCMILLAN RD
Project NameSpring Creek Boise Senior Livi
Customer Number 
ePlanReview 
Description
This fire alarm permit is to provide a new automatic and manual detection system in a new assisted living building. This system shall provide full area smoke detection, full notification, and sprinkler system monitoring. No duct detectors were shown as needed and are not part of this permit scope.

Associated building permit: BLD08-00698 ("SPRING CREEK BOISE" Senior Assisted Living) -This building is fully sprinklered for allowable area increase and occupancy use group. To construct a 16,311 sq. ft., Type VA construction, one story Assisted residential living facility building with 29 sleeping units with common associated use dining, kitchen, living room, salon, mechanical & accessible common use restroom / powder room support areas; construct a 1-hour fire-resistive rated exit corridor to serve all areas of the building, with fire rated protection of penetrations and self-closing, "S" label smoke/fire doors for opening protection; electrical, mechanical, plumbing, sprinkler and alarm installation; a minimum of 2 fully Accessible Units and all others complying as Type 'B' accessible units or better. All per approved plans to include red-line notes and all attached plan reviews of all reviewing agencies. DRH07-00476 CUP07-00175 drs
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  5/11/2009 DONE
Plans taken to records to scan
INSP-Final Inspection12/1/200812/1/200812/1/2008PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Alarm Testing11/24/200811/25/200811/25/2008PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Alarm Testing11/21/200811/24/200811/24/2008PFAIL
DetailsTroy Cobbley
The smoke detectors have been relocated but I found that the signals are not going out to the monitoring station. The testing of all devices will need to be redone
INSP-Final Inspection11/20/200811/21/200811/21/2008AFAIL
DetailsTroy Cobbley
Smoke detectors located in all two bedroom units are located less than three feet from bathroom door containing a shower, corrections will have to be made to final permit. All other testing has been completed. KR
Issue and Print Permit  9/3/2008 DONE
DetailsTisha Gallop
Alarm Plan Check  9/2/2008 PASS
See redlined drawings and review comments
PLANS/APPL TAKEN TO FRONT DESK  9/2/2008 DONE
Inspection Record Card- Fire9/2/2008 9/2/2008 DONE
Details
Telephone call  9/2/2008 DONE
Details
t/c w rand at ###-#### - permit ready and no fees due
Permit Ready to Issue  9/2/2008 DONE
Details
Application received  8/26/2008  
DetailsMarsha Smylie
Plan assigned to (Stephanie)8/26/2008 8/26/2008 DONE
DetailsStephanie L. Cobbley