Permit Information
Permit NumberFIR08-00603
StatusFinaled
Name SIMPLEX GRINNELL
Site Address 7557 W USTICK RD
Project NameWest Branch Public Library
Customer Number 
ePlanReview 
Description
This fire alarm permit is to provide a new required manual fire alarm system in a new building. This permit scope shall include pull stations, full area automatic smoke detection for HVAC shutdown, notification, sprinkler system monitoring, and motorized shade operation.

Associated building permit: BLD08-00475 West Boise Public Library - To construct a new 14,860 square foot, one story, steel framed public library building and related site improvements. This building is fully fire sprinkled. The sprinklers are used for area increase and A-3 Occupancy requirements. This building was reviewed as nonseparated uses with the A-3 Occupancy being the most restrictive. All construction per the approved plans and attached comment list. JCM
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  7/17/2009 DONE
Taken to records for scanning.
INSP-Final Inspection6/9/20096/10/20096/10/2009APASS
DetailsTroy Cobbley
permit passed
INSP-Final Inspection6/8/20096/9/20096/9/2009AFAIL
DetailsTroy Cobbley
All items tested ok except for the hvac interconnect has not been terminated. The curtains in the south east room rolled up under alarm but the curtains in the main library room did not. Another inspection fee is to be applied.
INSP-Final Inspection6/6/20096/8/20096/8/2009AFAIL
DetailsTroy Cobbley
I arrived at the project and was notified by mark that the monitoring had not been set up/finalized with Apex. A re-inspection fee has been applied for any future inspections.
INSP-Final Inspection6/3/20096/4/20096/5/2009AFAIL
DetailsTroy Cobbley
No inspection was performed. The monitoring had not been set up completely, manual pull stations are mounted too high, door holders had not been completely installed and wired into the fire alarm panel, an hvac control wire was not connected to the panel yet and an electrical/fire alarm box behind the wet sprinkler riser did not have a cover installed. These are just items noted initially and is not a complete list of possible corrections needed.
FIR-Aging Inspection12/19/200812/19/200812/19/2008 DONE
DetailsForrest France
Building construction underway, work in progress.
Issue and Print Permit  9/19/2008  
Alarm Plan Check  9/18/2008 PASS
PLANS/APPL TAKEN TO FRONT DESK  9/18/2008 DONE
Inspection Record Card- Fire9/18/2008 9/18/2008 DONE
Details
Telephone call  9/18/2008 DONE
Details
left vm for charlie bayne at ###-#### - permit ready and fees given
Permit Ready to Issue  9/18/2008 DONE
Details
Miscellaneous action  9/17/2008 DONE
Recieved letter from the Engineer
Telephone call  9/5/2008 DONE
Spoke to Charlie and let him know I need a letter from the Engineer that he has reviewed the plans and it meets the intended design. He stated he thought that was only for TI's and not new, and that he would contact the engineer right away. I told him I would just set the plans aside for a couple of days and then follow up.
Application received  8/26/2008  
Plan assigned to (Stephanie)8/26/2008 8/26/2008 DONE
DetailsStephanie L. Cobbley
Case Summary  8/26/2008 DONE