Permit Information
Permit NumberFIR08-00607
StatusFinaled
Name R M E INC
Site Address 7201 W FAIRVIEW AVE
Project NameBURLINGTON COAT FACTORY
Customer Number 
ePlanReview 
Description
This fire alarm permit is to install a new manual fire alarm system in an existing building. Permit includes pull stations, notification, duct detector monitoring, and sprinkler system monitoring.

Associated building permit: BLD08-01467 (BURLINGTON COAT FACTORY) Permit to remodel a 65,551 square foot tenant space and make cosmetic exterior changes per approved plans and CZC08-00104. Work to include: [Demolition of existing floor coverings, existing storefront, interior non-bearing walls,] {construction of interior non-bearing walls to create new accessible restrooms, a count room, a cash office, a managers office, a break room,} new flooring throughout, new cash wraps, new storefront system, and interior finishes in compliance with chapter 8 of the IBC. This building is fully fire sprinklered for area increase any alterations or modifications to the sprinkler system WILL REQUIRE A SEPARATE PERMIT and shall be installed per NFPA #13 as regulated by the fire department. **TLW**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Case Summary  8/8/2016 DONE
Miscellaneous action  5/11/2009 DONE
Plans taken to records to scan
INSP-Final Inspection4/6/20094/6/20094/6/2009PPASS
DetailsTroy Cobbley
Permit finaled. It took two visits to the job site before the inspection could be passed. At the first inspection it was found that the incorrect sample tubes for the duct smoke detectors had been installed. The correct sample tube were found, installed and verified this afternoon.
INSP-Alarm Testing4/6/20094/6/20094/6/2009APASS
DetailsTroy Cobbley
It took two visits to the job site before the inspection could be passed. At the first inspection it was found that the incorrect sample tubes for the duct smoke detectors had been installed. The correct sample tube were found, installed and verified this afternoon.
INSP-Final Inspection3/31/20094/1/20094/1/2009AFAIL
DetailsTroy Cobbley
The spacing of the strobes has been corrected but functionality was not tested. None of the duct smoke detectors tested shutdown upon detection of smoke. The correct orfices need to be installed in both of the fire sprinkler inspector test lines. The flow switch on the east system did not operate. The west sprinkler system flow switch was not tested. The outside alarm bell did not operate on the east sprinkler system. The sprinkler tamper switches did operate correctly.
INSP-Alarm Testing3/30/20093/31/20093/31/2009ACANC
DetailsTroy Cobbley
Cnceled due to time constraints
INSP-Alarm Testing3/26/20093/27/20093/27/2009AFAIL
DetailsTroy Cobbley
The only items tested today were the phone lines for supervision. They were programed for the supervision as I waited. The interconnect with the NAC panel was also tested. The Inspection did not proceed any further due to many of the strobes being overspaced. Spacing will need to be modified or additional strobes added. The phone line trouble signals did report to the monitoring station.
Inspection Record Card- Fire2/25/2009 2/25/2009 DONE
Details
Telephone call  2/25/2009 DONE
Details
t/c w sean at ###-#### - permit ready
Permit Ready to Issue  2/25/2009 DONE
Details
(F) Reprint permit  2/25/2009 DONE
CHANGE STATUS TO (ISS)  2/25/2009 DONE
Alarm Plan Check2/24/2009 2/24/2009 PASS
DetailsStephanie L. Cobbley
Plan modification to add 8 duct detectors is approved without additional comments.
PLANS/APPL TAKEN TO FRONT DESK  2/24/2009 DONE
Approved plan modification documents available at front counter (taken up at 5:19pm)
Inspection Record Card- Fire1/29/2009 1/29/2009 DONE
Details
Telephone call  1/29/2009 DONE
Details
t/c w sean at ###-#### - permit ready and fees given
Permit Ready to Issue  1/29/2009 DONE
Details
Issue and Print Permit  1/29/2009 DONE
Alarm Plan Check  1/28/2009 PASS
See redlines and review comments
PLANS/APPL TAKEN TO FRONT DESK  1/28/2009 DONE
Plan resubmittals received  1/20/2009 DONE
DetailsAlexandra L. DeYoung
Plan mod rec'd- two copies of app and plans- taken to fire review
Plan assigned to (Stephanie)1/20/2009 1/20/2009 DONE
DetailsStephanie L. Cobbley
Alarm Plan Check  9/5/2008 FAIL
Please see redlines and review comments
PLANS/APPL TAKEN TO FRONT DESK  9/5/2008 DONE
Submittals available at front desk for contractor pick-up
Telephone call  9/5/2008 DONE
Left a message for Rob letting him know the plans were being denied and a brief summery of why.
Miscellaneous action  9/5/2008 DONE
Faxed review comments to Rob Ahten
Application received  8/27/2008  
Plan assigned to (Stephanie)8/27/2008 8/27/2008 DONE
DetailsStephanie L. Cobbley
Case Summary  8/27/2008 DONE