Miscellaneous action | | | 5/11/2009 | | DONE |
|
|
|
Plans taken to records to scan
|
INSP-Final Inspection | 11/3/2008 | 11/4/2008 | 11/4/2008 | A | PASS |
Forrest France
|
|
|
Items on C/N finished, fire alarm work passed field inspection, permit finaled.
|
INSP-Final Inspection | 11/3/2008 | 11/3/2008 | 11/3/2008 | P | FAIL |
Forrest France
|
|
|
Need to provide signage at the door to the relocated FACP room, missing three junction box covers-two at the 2nd floor one at the 1st floor, noted the outside sprinkler waterflow bell is not functional. Notification, manual pulls, signals recieved, nac and main panel tested okay.
|
INSP-Final Inspection | 10/31/2008 | 10/31/2008 | 10/31/2008 | P | NR |
Forrest France
|
|
|
This job was not ready to be inspected. Panel was in trouble due to close tampers, existing wires that were not being used and were not for future devices needs to be removed.They will call in for an am inspection so we can test devices in existing bussiness due to relocation of panel. kr
|
INSP-Final Inspection | 10/30/2008 | 10/30/2008 | 10/30/2008 | P | NR |
Forrest France
|
|
|
Noted trouble at the panel due to nac fault, three sprinkler tampers closed due to work in progress,system is not ready for final inspection at this time.
|
Alarm Plan Check | | | 10/28/2008 | | PASS |
|
|
|
Plan modification review done - pass
|
PLANS/APPL TAKEN TO FRONT DESK | | | 10/28/2008 | | DONE |
|
|
|
|
Override - Parcel Holds | | | 10/28/2008 | | |
|
|
|
|
Inspection Record Card- Fire | 10/28/2008 | | 10/28/2008 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 10/28/2008 | | DONE |
|
|
|
t/c w charlie bayne at ###-#### - permit ready and fees given
|
Override - Parcel Holds | | | 10/28/2008 | | |
|
|
|
|
Permit Ready to Issue | | | 10/28/2008 | | DONE |
|
|
|
|
CHANGE STATUS TO (ISS) | | | 10/28/2008 | | DONE |
Alexandra L. DeYoung
|
|
|
|
Plan assigned to (Stephanie) | 10/23/2008 | | 10/23/2008 | | DONE |
Stephanie L. Cobbley
|
|
|
|
Plan resubmittals received | | | 10/20/2008 | | DONE |
|
|
|
Received 1 applicationand 2 copies of sheets 1 OF 4 ,2 OF 4,3 OF 4,4 OF 4 sent to fire ///dld
|
Issue and Print Permit | | | 9/12/2008 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 9/11/2008 | | 9/11/2008 | | DONE |
|
|
|
|
Telephone call | | | 9/11/2008 | | DONE |
|
|
|
left message with laurie for charlie bayne at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 9/11/2008 | | DONE |
|
|
|
|
Alarm Plan Check | | | 9/10/2008 | | PASS |
|
|
|
Please see redlined drawings and review comments
|
PLANS/APPL TAKEN TO FRONT DESK | | | 9/10/2008 | | DONE |
|
|
|
|
Application received | | | 9/3/2008 | | |
|
|
|
|
Plan assigned to (Stephanie) | 9/3/2008 | | 9/3/2008 | | DONE |
Stephanie L. Cobbley
|
|
|
|
Case Summary | | | 9/3/2008 | | DONE |
|
|
|
|