Information based on query as of Friday, July 5, 2024.
Permit Information
Permit NumberFIR08-00639
StatusFinaled
Name SIMPLEX GRINNELL
Site Address 1130 N ALLUMBAUGH ST
Project NameValley View Independant Living
Customer Number 
ePlanReview 
Description
Scope of Work: UG Only - The fire sprinkler contractor will demo the existing FDC and install a remote FDC in accordance with the plans dated 09/15/2008 know as revision 5. The fire sprinkler underground work shall comply with NFPA 13-2007, NFPA 24-2007 the IFC-2006, attached review comment and conditions list, as regulated by the Fire Chief. These notes, permit and fire “Inspection Card” are required to be on site as a condition of this work, to provide witness of compliance verification of minimum fire code. This permit is attached to building permit: BLD07-01834. The overhead will be submitted under a separate permit.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/6/200910/6/200910/6/2009PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Supply line flush10/15/200810/15/200810/15/2008PPASS
DetailsTroy Cobbley
Flush Under ground FDC piping.KR
INSP-Supply line flush10/14/200810/15/200810/15/2008ANR
DetailsTroy Cobbley
Will call this permit in tomorrow. Can not shut down system to make final connection until fire watch is in place. KR
INSP-Sprinkler Rough-in10/10/200810/14/200810/14/2008APASS
DetailsTroy Cobbley
The underground hydro test for the north relocated remote FDC passed.
INSP-Sprinkler Rough-in10/9/200810/10/200810/10/2008ACANC
DetailsTroy Cobbley
To be rescheduled. Piping was not buried yet so that the hydro test could be performed.
INSP-Sprinkler Rough-in10/6/200810/9/200810/9/2008PDONE
DetailsTroy Cobbley
Ok to cover underground FDC.KR
PLANS/APPL TAKEN TO FRONT DESK  9/25/2008 DONE
Inspection Record Card- Fire9/25/2008 9/25/2008 DONE
Details
Telephone call  9/25/2008 DONE
Details
t/c w brad bettencourt at ###-#### -permit ready and fees given
Permit Ready to Issue  9/25/2008 DONE
Details
Issue and Print Permit  9/25/2008 DONE
Sprinkler Plan Check9/16/2008 9/24/2008 PASS
Details
plans are approved
Application received  9/16/2008  
DetailsMarsha Smylie
Case Summary  9/16/2008 DONE
DetailsMarsha Smylie
Plan assigned to (SAM)9/16/2008    
DetailsSam Rogers