Miscellaneous action | | | 6/3/2009 | | DONE |
|
|
|
Taken to records for scanning
|
INSP-Final Inspection | 5/25/2009 | 5/26/2009 | 5/26/2009 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled. The address has been changed from Hartman to Liberty.
|
INSP-Final Inspection | 5/21/2009 | 5/21/2009 | 5/21/2009 | P | FAIL |
Troy Cobbley
|
|
|
All items have been tested except the elevator recall/voltage monitoring interconnections.
|
Inspection Record Card- Fire | 5/21/2009 | | 5/21/2009 | | DONE |
|
|
|
|
Telephone call | | | 5/21/2009 | | DONE |
|
|
|
customer came in and picked up permit
|
Permit Ready to Issue | | | 5/21/2009 | | DONE |
|
|
|
|
Issue and Print Permit | | | 5/21/2009 | | DONE |
|
|
|
|
INSP-Final Inspection | 5/19/2009 | 5/20/2009 | 5/20/2009 | A | CANC |
Troy Cobbley
|
|
|
See yesterdays entry for details.
|
Plan assigned to (Stephanie) | 5/20/2009 | | 5/20/2009 | | DONE |
Stephanie L. Cobbley
|
|
|
5/20/2009 16:06:58 SLC - activity updated through activity FIRA24 from case FIR08-00679.
|
Plan resubmittals received | | | 5/20/2009 | | |
Stephanie L. Cobbley
|
|
|
|
Alarm Plan Check | 5/20/2009 | | 5/20/2009 | | PASS |
Stephanie L. Cobbley
|
|
|
See redlines and review comments
|
PLANS TAKEN FRONT DESK ALARM | | | 5/20/2009 | | DONE |
|
|
|
Approved redlined plans available at front counter
|
INSP-Alarm Testing | 5/19/2009 | 5/19/2009 | 5/19/2009 | P | FAIL |
Troy Cobbley
|
|
|
Resubmittals are required due to addressable notification devices installed instead of the standard devices. Also the smoke detectors model shown on the plans is not what has been installed. The initiating devices in the elevator shaft have been deleted per the state elevator inspector per brian with simplex. As-builts were on site but did not match the installation. The strobes on the second floor exterior balcony need modified to provide correct coverage. The manual pull station in the first floor lobby is mounted too high. The items tested that passed are phone lines, battery trouble, loss of a/c and the smoke detector over the facp. These signals were received at the central station. I request a manometer test of the duct smoke detectors on the first floor due to questionable positioning in the ducting.
|
FIR-Aging Inspection | 1/13/2009 | 1/13/2009 | 1/16/2009 | | NR |
Troy Cobbley
|
|
|
Work is in progress
|
Inspection Record Card- Fire | 10/14/2008 | | 10/14/2008 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 10/14/2008 | | DONE |
|
|
|
left message w laura for charlie bayne at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 10/14/2008 | | DONE |
|
|
|
|
Issue and Print Permit | | | 10/14/2008 | | DONE |
|
|
|
|
Alarm Plan Check | | | 10/13/2008 | | PASS |
|
|
|
See redlines on drawings and review comments
|
PLANS/APPL TAKEN TO FRONT DESK | | | 10/13/2008 | | DONE |
|
|
|
|
Application received | | | 10/2/2008 | | |
Marsha Smylie
|
|
|
|
Plan assigned to (Stephanie) | 10/2/2008 | | 10/2/2008 | | DONE |
Stephanie L. Cobbley
|
|
|
|
Case Summary | | | 10/2/2008 | | |
|
|
|
|