Miscellaneous action | | | 5/11/2009 | | DONE |
|
|
|
Plans taken to records to scan
|
INSP-Final Inspection | 11/25/2008 | 11/26/2008 | 11/26/2008 | A | PASS |
Forrest France
|
|
|
Items on C/N completed, fire alarm permit finaled.
|
Telephone call | | | 11/26/2008 | | DONE |
|
|
|
Telcon from Jason Minnick, AEI, ###-####; they have relocated all speaker/strobe appliances within the TI space to proper mounting height except one at end of a corridor which is mounted 1" too low, but embedded in the RC wall of the exit stairwell (205). I gave approval for this device to remain in its current location due to practical difficulties to relocate (installed ~1###-####) and peripheral coverage from an adjacent 30cd strobe within the near vicinity.
|
INSP-Final Inspection | 11/6/2008 | 11/7/2008 | 11/7/2008 | A | FAIL |
Forrest France
|
|
|
Noted wall mounted notification appliances are installed below min. height allowed per NFPA 72, see also red line comments on stamped plans for necessary field modifications.
|
Issue and Print Permit | | | 10/17/2008 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 10/15/2008 | | 10/15/2008 | | DONE |
|
|
|
|
Telephone call | | | 10/15/2008 | | DONE |
|
|
|
t/c w jason minnick at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 10/15/2008 | | DONE |
|
|
|
|
Alarm Plan Check | | | 10/14/2008 | | PASS |
|
|
|
See redlines and review comments
|
PLANS/APPL TAKEN TO FRONT DESK | | | 10/14/2008 | | DONE |
|
|
|
|
Application received | | | 10/2/2008 | | DONE |
|
|
|
|
Case Summary | | | 10/2/2008 | | |
|
|
|
|