Information based on query as of Friday, July 5, 2024.
Permit Information
Permit NumberFIR08-00680
StatusFinaled
Name AUDIO ELECTRONICS INC
Site Address 250 S 5TH ST
Project NameTHORTON OLIVER KELLER 2ND FLR
Customer Number 
ePlanReview 
Description
This fire alarm permit is to add/relocate speaker/strobe and strobe only notification as needed to accommodate a tenant improvement. Some devices are being replaced with new to ensure synchronization is provided. Other existing devices (i.e. the stairwells etc…) are to remain because they do not effect the synchronization of the other devices in the tenant space. No initiating devices are part of this permit scope.

Associated building permit: BLD08-01460 (THORTON OLIVER KELLER - 2nd floor - C W Moore Plaza) Permit to remodel an existing 11,009 square foot office tenant space. Work to include: [Construction of interior non-bearing partition walls to create four offices out of two offices, to enlarge the open office area and reduce the break room square footage, and to enlarge an existing IT/Server room,] new doors in specified locations, install new H-VAC including ducts and diffusers, new electrical, and installation of interior finishes in compliance with chapter 8 of the IBC. This building is sprinklered for area increase any alterations or modifications to the sprinkler system WILL REQUIRE A SEPARATE PERMIT and shall be maintained as regulated by the fire department in accordance with NFPA 13 standards. **TLW**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  5/11/2009 DONE
Plans taken to records to scan
INSP-Final Inspection11/25/200811/26/200811/26/2008APASS
DetailsForrest France
Items on C/N completed, fire alarm permit finaled.
Telephone call  11/26/2008 DONE
Telcon from Jason Minnick, AEI, ###-####; they have relocated all speaker/strobe appliances within the TI space to proper mounting height except one at end of a corridor which is mounted 1" too low, but embedded in the RC wall of the exit stairwell (205). I gave approval for this device to remain in its current location due to practical difficulties to relocate (installed ~1###-####) and peripheral coverage from an adjacent 30cd strobe within the near vicinity.
INSP-Final Inspection11/6/200811/7/200811/7/2008AFAIL
DetailsForrest France
Noted wall mounted notification appliances are installed below min. height allowed per NFPA 72, see also red line comments on stamped plans for necessary field modifications.
Issue and Print Permit  10/17/2008 DONE
Inspection Record Card- Fire10/15/2008 10/15/2008 DONE
Details
Telephone call  10/15/2008 DONE
Details
t/c w jason minnick at ###-#### - permit ready and fees given
Permit Ready to Issue  10/15/2008 DONE
Details
Alarm Plan Check  10/14/2008 PASS
See redlines and review comments
PLANS/APPL TAKEN TO FRONT DESK  10/14/2008 DONE
Application received  10/2/2008 DONE
Case Summary  10/2/2008