Miscellaneous action | | | 1/5/2010 | | DONE |
Tim Frost
|
|
|
Drawings sent for scanning.
|
INSP-Final Inspection | 10/27/2009 | 10/27/2009 | 10/27/2009 | P | PASS |
Forrest France
|
|
|
Fire sprinkler permit work final approved.
|
INSP-Sprinkler Rough-in | 10/15/2009 | 10/15/2009 | 10/15/2009 | P | FAIL |
Troy Cobbley
|
|
|
The inspection was for the new dental area. The plans show three extended coverage pendants in this area but standard coverage have been installed instead. I was ok with this since it is not a remote area and coverage seems adequate. The problem is two wood beams have been installed above the ceiling where the upright protection has been removed. Sam Ball, myself and the general contractor talked about options.
|
CHANGE STATUS TO (ISS) | | | 10/15/2009 | | DONE |
|
|
|
|
INSP-Final Inspection | 8/18/2009 | 8/18/2009 | 8/19/2009 | P | PASS |
Forrest France
|
|
|
Sprinkler monitoring, forward flow, C/N items, final walkthrough passed, contractor to call in UG permit for final as discussed, one missing escutcheon installed while on site, head guards at the mezzanine to be in place prior to building final, unfinished dentist office protected with uprights at the deck and provided with area separation.
|
INSP-Final Inspection | 8/17/2009 | 8/17/2009 | 8/18/2009 | P | NR |
Forrest France
|
|
|
Project related fire alarm permit work is not ready for testing.
|
INSP-Sprinkler Rough-in | 8/11/2009 | 8/12/2009 | 8/12/2009 | A | PART |
Forrest France
|
|
|
Completed inspection for mechanical mezzanine areas, protection at entry overbuilds, storage rooms, and the dental office. Need to adjust upright coverage at the dental office and provide area separation at the east wall for interm shell protection, adjust one blocked upright at the mech. catwalk, discussed items for final including forward flow, riser supervison, final walkthrough, etc.
|
INSP-Sprinkler Rough-in | 8/11/2009 | 8/11/2009 | 8/12/2009 | P | PART |
Forrest France
|
|
|
mike Phone #: ###-####
|
INSP-Conference | 8/10/2009 | 8/10/2009 | 8/10/2009 | A | DONE |
Forrest France
|
|
|
Regarding items needed for project finals.
|
INSP-Sprinkler Rough-in/Hydro | 7/20/2009 | 7/20/2009 | 7/20/2009 | P | PART |
Forrest France
|
|
|
Overhead hydrostatic testing for both wet systems at the riser manifold passed.
|
INSP-Sprinkler Rough-in/Hydro | 7/17/2009 | 7/20/2009 | 7/20/2009 | A | PART |
Forrest France
|
|
|
Overhead install at the kitchen area drop ceilings approved for cover, need to foam dry pendent penetrations at the freezer, non-sprinklered cavity at the east side exterior canopy verified for insulation fill per NFPA exception allowed.
|
INSP-Sprinkler Rough-in | 6/22/2009 | 6/22/2009 | 6/22/2009 | P | PART |
Forrest France
|
|
|
Initialed and dated plans where grid ceiling areas are approved for cover including the library and administration offices.
|
INSP-Sprinkler Rough-in | 6/9/2009 | 6/9/2009 | 6/11/2009 | P | PART |
Forrest France
|
|
|
Classroom wings approved for drop ceiling cover, cafeteria and gym rough-in okayed, see plans for annotations.
|
INSP-Sprinkler Rough-in | 5/20/2009 | 5/21/2009 | 5/21/2009 | A | PART |
Forrest France
|
|
|
See notations marked on plans with initials and todays date for several rooms okayed for sheetrock ceiling cover first floor south side.
|
INSP-Sprinkler Rough-in | 4/22/2009 | 4/22/2009 | 4/22/2009 | P | PART |
Forrest France
|
|
|
Inspection for overhead cover at attic branchlines and upright heads at the kitchen, multi-use, front office and mechanical areas okayed for cover-See annotations on plans with today's date. Seismic bracing not yet installed to be verified at next inspection. Discussed field changes at the gym due to ceiling finishes and record drawings to be provided.
|
INSP-Sprinkler Rough-in | 4/15/2009 | 4/16/2009 | 4/16/2009 | P | PASS |
Troy Cobbley
|
|
|
See the city approved plans for locations where the sprinkler piping is ok for cover. These locations will have todays date and my initials.
|
INSP-Sprinkler Rough-in | 3/17/2009 | 3/18/2009 | 3/18/2009 | A | PART |
Forrest France
|
|
|
See plans marked for rough-in inspection completed today including three seismic braces to be added as discussed.
|
INSP-Sprinkler Rough-in | 3/12/2009 | 3/13/2009 | 3/13/2009 | A | PART |
Forrest France
|
|
|
OH rough-in okayed at the administration area and hard lid ceilings per plan annotations marked with today's date.
|
INSP-Sprinkler Rough-in | 3/2/2009 | 3/3/2009 | 3/3/2009 | A | PART |
Forrest France
|
|
|
Inspection for overhead work at sheetrock ceilings in restrooms area "A" approved for cover-locations also marked on plans. Also discussed exceptions allowed per NFPA 13 for non-sprinklered canopies and concealed spaces at the exterior portions of the building.
|
INSP-Sprinkler Rough-in | 2/17/2009 | 2/18/2009 | 2/18/2009 | A | PART |
Forrest France
|
|
|
Rough-in approved for cover per red lines on sheet FP-3 (east classroom wing).
|
INSP-Sprinkler Rough-in | 1/30/2009 | 1/30/2009 | 1/30/2009 | P | PART |
Forrest France
|
|
|
OH installation at classroom wing as marked on plan set sheet FP2 including exceptions okayed for cover.
|
FIR-Aging Inspection | 1/28/2009 | 1/28/2009 | 1/28/2009 | | DONE |
Forrest France
|
|
|
Work in progress.
|
Issue permit | | | 10/29/2008 | | |
|
|
|
|
Sprinkler Plan Check | 10/13/2008 | | 10/28/2008 | | PASS |
|
|
|
Plans & calculations are approved by Bryan Johnson
|
PLANS/APPL TAKEN TO FRONT DESK | | | 10/28/2008 | | |
Cathy Brown
|
|
|
|
Inspection Record Card- Fire | 10/28/2008 | | 10/28/2008 | | DONE |
Cathy Brown
|
|
|
|
Telephone call | | | 10/28/2008 | | DONE |
Cathy Brown
|
|
|
tlk to greg johnson ###-#### that permit and fees are ready to be picked up
|
Permit Ready to Issue | | | 10/28/2008 | | DONE |
Cathy Brown
|
|
|
|
Case Summary | | | 10/13/2008 | | DONE |
|
|
|
|
Application received | | | 10/13/2008 | | |
|
|
|
|
Pending Assignment by SAM | 10/13/2008 | | | | |
|
|
|
|