Miscellaneous action | | | 5/11/2009 | | DONE |
|
|
|
Plans taken to records to scan
|
INSP-Final Inspection | 1/8/2009 | 1/13/2009 | 1/13/2009 | A | PASS |
Troy Cobbley
|
|
|
permit finaled
|
INSP-Alarm Testing | 1/6/2009 | 1/8/2009 | 1/8/2009 | A | FAIL |
Troy Cobbley
|
|
|
See the city approved plans for locations of deficiencies which include all of the strobes in the storage areas being mounted too high, alot of the strobes over the main sales floor are overspaced off of the walls and the strobes in the deli area are overspaced. None of the audio/visual devices were tested for operation. As-built will be required showing any additional devices. The NAC panels have been tested for interconnection to the existing facp.
|
INSP-Final Inspection | 1/8/2009 | 1/9/2009 | 1/8/2009 | P | CANC |
Troy Cobbley
|
|
|
Scheduled by a contractor via Hello! on 1/8/2009 at 3:18:26 PM. Contact: ###-####. Disp set to [CANC] by a contractor via Hello! on Jan 8 2009 3:35PM.
|
Issue and Print Permit | | | 12/15/2008 | | DONE |
Alexandra L. DeYoung
|
|
|
|
Inspection Record Card- Fire | 12/10/2008 | | 12/10/2008 | | DONE |
|
|
|
|
Telephone call | | | 12/10/2008 | | DONE |
|
|
|
left vm for jan senior at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 12/10/2008 | | DONE |
|
|
|
|
Alarm Plan Check | | | 12/9/2008 | | PASS |
|
|
|
See review comments
|
PLANS/APPL TAKEN TO FRONT DESK | | | 12/9/2008 | | DONE |
|
|
|
|
Plan resubmittals received | | | 12/2/2008 | | |
|
|
|
received application & "2" sets of plans-- took plans to Stephanie C.
|
Plan assigned to (Stephanie) | 12/2/2008 | | 12/2/2008 | | DONE |
Stephanie L. Cobbley
|
|
|
|
Alarm Plan Check | | | 10/23/2008 | | FAIL |
|
|
|
See redlined plans and review comments
|
PLANS/APPL TAKEN TO FRONT DESK | | | 10/23/2008 | | DONE |
|
|
|
Redlined plans at front counter for contractor pick-up
|
Miscellaneous action | | | 10/23/2008 | | DONE |
|
|
|
Faxed review comments to contractor
|
Application received | | | 10/15/2008 | | |
|
|
|
|
Plan assigned to (Stephanie) | 10/15/2008 | | 10/15/2008 | | DONE |
Stephanie L. Cobbley
|
|
|
|