Miscellaneous action | | | 5/11/2009 | | DONE |
|
|
|
Plans taken to records to scan
|
INSP-Final Inspection | 1/27/2009 | 1/28/2009 | 1/28/2009 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
Override - Parcel Holds | | | 1/27/2009 | | |
|
|
|
|
INSP-Alarm Testing | 11/10/2008 | 11/10/2008 | 11/10/2008 | A | PART |
Troy Cobbley
|
|
|
The fire alarm testing in the areas south of the main lobby passed.
|
Inspection Record Card- Fire | 10/24/2008 | | 10/24/2008 | | DONE |
|
|
|
|
Telephone call | | | 10/24/2008 | | DONE |
|
|
|
t/c w charlie bayne at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 10/24/2008 | | DONE |
|
|
|
|
Issue and Print Permit | | | 10/24/2008 | | DONE |
|
|
|
|
Alarm Plan Check | | | 10/23/2008 | | PASS |
|
|
|
See redlined plans and review comments
|
PLANS/APPL TAKEN TO FRONT DESK | | | 10/23/2008 | | DONE |
|
|
|
|
Application received | | | 10/17/2008 | | |
|
|
|
|
Plan assigned to (Stephanie) | 10/17/2008 | | 10/17/2008 | | DONE |
Stephanie L. Cobbley
|
|
|
|