Permit NumberFIR08-00710
StatusFinaled
Name DEBEST FIRE PROTECTION
Site Address 12055 W USTICK RD
Project NameSPR-Dr Steph & Robertson Med
Customer Number 
ePlanReview 
Description
To install 1 fire sprinkler head in new med gas closet. This work is associated with BLD08-03229.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/31/200810/31/200810/31/2008PPASS
DetailsTroy Cobbley
Per phone call with Troy ok to pass final inspection
DOC - Permit Finaled  10/31/2008 DONE
INSP-Sprinkler Rough-in/Hydro10/28/200810/29/200810/29/2008APASS
DetailsTroy Cobbley
permit finaled
INSP-Sprinkler Rough-in/Hydro10/27/200810/28/200810/28/2008AFAIL
DetailsTroy Cobbley
The sidewall head is mounted too far off of the wall and the backflow preventor needs to be certified. Per the sprinkler contractor a standard sidewall was going to be installed and a heat vent installed in this room to keep the temp above 40 degrees.
Issue and Print Permit  10/23/2008 DONE
Sprinkler Plan Check10/21/2008 10/22/2008 PASS
DetailsScott Arellano
Med gas closet. Plan with Sam Rogers.
PLANS/APPL TAKEN TO FRONT DESK  10/22/2008 DONE
Inspection Record Card- Fire10/22/2008 10/22/2008 DONE
Details
Telephone call  10/22/2008 DONE
Details
t/c w shaun ramsey at ###-#### x 226 - permit ready and fees given
Permit Ready to Issue  10/22/2008 DONE
Details
Application received  10/20/2008  
Pending Assignment by SAM10/20/2008