Permit Information
Permit NumberFIR08-00740
StatusFinaled
Name FIRE SENTRY SYSTEMS
Site Address 8580 W USTICK RD
Project Name LITTLE SCHOLAR'S WEST
Customer Number 
ePlanReview 
Description
This fire alarm permit is to replace an obsolete fire alarm control panel with new and to upgrade the existing manual fire alarm system to meet current code requirements. There is no associated building permit.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  5/11/2009 DONE
Plans taken to records to scan
INSP-Final Inspection4/2/20094/3/20094/3/2009APASS
DetailsTroy Cobbley
Permit finaled
Telephone call  3/26/2009 DONE
Spoke with Earl who thought the project had already been finaled. After informing him that the last final inspection done had failed, he stated that he would be calling in for a final next week when John was back in the office.
INSP-Final Inspection12/5/200812/5/200812/5/2008PFAIL
DetailsTroy Cobbley
The alarm system as installed has been tested. The strobes in classroom #4 were changed to 75cd to meet NFPA 72 spacing requirements and end of line voltages verified. I have deferred the requirements of off site monitoring and the annunciation of a trouble signal at the remote annunciatior to the fire alarm plan reviewer and sam rogers. I also had earle lower the manual pull stations to a maximum height of 48".
Miscellaneous action  12/5/2008 DONE
In light of the circumstances of Little Scholar's Daycare, we are going to allow the following in regards to the fire alarm system:
1) Monitoring (a dialer/phone lines) will not be required in this situation. The initial impression at the time of the fire alarm plan review was that the original panel dialed out for monitoring the system, therefore it was understood that the new panel would also have to dial out. After further discussions, and realizing the fact that the original panel did not dial out, for this particular project we will allow this panel to remain a non-monitored system.
2) Under the circumstances of this particular permit, we will allow you to remove the annunciator panel. If you choose not to remove the annunciator panel, then you shall be required to make it fully functional (connect the trouble).
This decision was made on a 'per-case' basis and will not alter other decisions made on existing or future permits.
Issue and Print Permit  11/14/2008 DONE
DetailsAlexandra L. DeYoung
Inspection Record Card- Fire11/13/2008 11/13/2008 DONE
Details
Telephone call  11/13/2008 DONE
Details
left message w rhona for john lopez at ###-#### - permit ready and fees given
Permit Ready to Issue  11/13/2008 DONE
Details
Alarm Plan Check  11/12/2008 PASS
see redlined plans and review comments
PLANS/APPL TAKEN TO FRONT DESK  11/12/2008 DONE
Application received  10/30/2008  
Plan assigned to (Stephanie)10/30/2008 10/30/2008 DONE
DetailsStephanie L. Cobbley