Miscellaneous action | | | 3/10/2010 | | DONE |
|
|
|
Sent to records for scanning
|
INSP-Final Inspection | 3/9/2010 | 3/9/2010 | 3/9/2010 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled.
|
INSP-Final Inspection | 2/3/2009 | 2/4/2009 | 2/4/2009 | P | PART |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Sprinkler Rough-in/Hydro | 2/3/2009 | 2/4/2009 | 2/4/2009 | P | PASS |
Troy Cobbley
|
|
|
The above ground hydro test passed.
|
INSP-Final Inspection | 1/29/2009 | 2/2/2009 | 2/2/2009 | A | FAIL |
Troy Cobbley
|
|
|
Provide hydro testing per NFPA 13 and 25. Provide data sheets for the newly installed valve on the backflow preventor. Provide as-builts.
|
INSP-Sprinkler Rough-in | 1/14/2009 | 1/15/2009 | 1/15/2009 | P | FAIL |
Troy Cobbley
|
|
|
Remove 1" valve or provide tamper switch on the valve controlling water to the elevator shaft. The upright sprinklers along column line "D" are overspaced by being 8'-0" off of the column line/roof deck transition. The tamper switch on the backflow preventor does not meet the requirements of NFPA 72. Several sprinkler pendants on the second floor are located too close to the supply registers. Standard responce upright heads have been mixed with new quick responce heads over the sales floor. Earthquake bracing is missing on the 4" main. An additional pendant head is needed in the first floor storage room. Provide sprinkler coverage under the landing at the west stairs.
|
INSP-Conference | 11/25/2008 | 11/26/2008 | 11/26/2008 | A | CANC |
Troy Cobbley
|
|
|
Cancel per Mike
|
Issue and Print Permit | | | 11/21/2008 | | DONE |
|
|
|
|
Sprinkler Plan Check | 11/14/2008 | | 11/20/2008 | | PASS |
|
|
|
Plans are approved by Bryan Johnson
|
PLANS/APPL TAKEN TO FRONT DESK | | | 11/20/2008 | | DONE |
Cathy Brown
|
|
|
|
Inspection Record Card- Fire | 11/20/2008 | | 11/20/2008 | | DONE |
Cathy Brown
|
|
|
|
Telephone call | | | 11/20/2008 | | DONE |
Cathy Brown
|
|
|
lft a message to secretary for lilly ###-#### that permit and fees are ready to be picked up
|
Permit Ready to Issue | | | 11/20/2008 | | DONE |
Cathy Brown
|
|
|
|
Inspection Record Card- Fire | 11/20/2008 | | 11/20/2008 | | DONE |
Cathy Brown
|
|
|
|
Application received | | | 11/14/2008 | | |
|
|
|
|
Pending Assignment by SAM | 11/14/2008 | | | | |
Sam Rogers
|
|
|
|