Miscellaneous action | | | 9/3/2009 | | DONE |
|
|
|
Fire alarm plans taken to records for scanning
|
INSP-Final Inspection | 8/14/2009 | 8/20/2009 | 8/21/2009 | A | PASS |
Forrest France
|
|
|
The remainder of fire alarm system testing passed per inspection by S. Cobbley, fire alarm permit approved for final.
|
INSP-Final Inspection | 8/14/2009 | 8/21/2009 | 8/21/2009 | A | CANC |
Forrest France
|
|
|
We would like to continue the inspection on this school this morning, and then continue through the rest of the week at approximately the same time if that will work. Thank you, Jason ###-#### Phone #: ###-#### Internet Inspection Request from: Jason Minnick Inspection cancelled from web by: Jason Minnick
|
INSP-Final Inspection | 8/14/2009 | 8/19/2009 | 8/20/2009 | A | PART |
Forrest France
|
|
|
See comments per inspection completed by S. Cobbley including areas A, B, D, correction items and adjustments to date.
|
INSP-Final Inspection | 8/14/2009 | 8/18/2009 | 8/19/2009 | A | PART |
Forrest France
|
|
|
Fire alarm testing for area "B" completed including correction notice items and notification throughout. Correction items from this inspection include two missing smoke detectors at the open junction boxes on the sloped ceiling in the cafeteria, provide notification for the modified floorplan at a classroom area "A" as noted, one SD at the corridor area A north end has not been relocated, switched addresses at two smoke detectors, sprinkler monitoring okayed.
|
INSP-Final Inspection | 8/14/2009 | 8/17/2009 | 8/18/2009 | A | FAIL |
Forrest France
|
|
|
See red line annotations on stamped plan set for locations of items in need of adjustment per on site discussion and jobsite walkthrough.
|
(F) Reprint permit | | | 8/14/2009 | | DONE |
|
|
|
|
CHANGE STATUS TO (ISS) | | | 8/14/2009 | | DONE |
|
|
|
|
Plan assigned to (Stephanie) | 8/11/2009 | | 8/13/2009 | | DONE |
Stephanie L. Cobbley
|
|
|
8/13/2009 14:38:37 SLC - activity updated through activity FIRA24 from case FIR08-00775.
|
1st review completed | | | 8/13/2009 | | DONE |
|
|
|
|
Alarm Plan Check | 8/13/2009 | | 8/13/2009 | | PASS |
Stephanie L. Cobbley
|
|
|
See redlines and review comments
|
PLANS TAKEN FRONT DESK ALARM | | | 8/13/2009 | | DONE |
|
|
|
Approved redlined plans available at front counter
|
Inspection Record Card- Fire | 8/13/2009 | | 8/13/2009 | | DONE |
|
|
|
|
Telephone call | | | 8/13/2009 | | DONE |
|
|
|
t/c w jason at ###-#### - permit (plan mod) ready and fees given
|
Permit Ready to Issue | | | 8/13/2009 | | DONE |
|
|
|
|
Plan resubmittals received | | | 8/11/2009 | | |
Tisha Gallop
|
|
|
received application and two copies of sheets S-1, E2.0F, E2.1F, E2.2F, E2.3F, E2.4F, FA-1, FA-2; routed to fire review
|
Telephone call | | | 8/5/2009 | | DONE |
|
|
|
Jason called regarding the addition of door holders and smoke detectors to trigger them. He wanted to know if he had to re-submit and get approved plans prior to doing the work. I let him know that since he already has an issued permit for that scope, that he did not have to get approved plans before doing the work, but he would have to resubmit a plan modification prior to calling for an inspection.
|
FIR-Aging Inspection | 5/13/2009 | 5/13/2009 | 5/13/2009 | | DONE |
Forrest France
|
|
|
Work in progress, construction underway.
|
CHANGE STATUS TO (ISS) | | | 5/12/2009 | | DONE |
|
|
|
|
(F) Reprint permit | | | 5/12/2009 | | |
|
|
|
|
Inspection Record Card- Fire | 3/13/2009 | | 3/13/2009 | | DONE |
|
|
|
|
Telephone call | | | 3/13/2009 | | DONE |
|
|
|
t/c w jason minnick at ###-#### - permit ready for pick up
|
Permit Ready to Issue | | | 3/13/2009 | | DONE |
|
|
|
|
Plan assigned to (Stephanie) | 3/5/2009 | | 3/12/2009 | | DONE |
Stephanie L. Cobbley
|
|
|
|
Alarm Plan Check | 3/12/2009 | | 3/12/2009 | | PASS |
Stephanie L. Cobbley
|
|
|
See redlines and review comments
|
PLANS/APPL TAKEN TO FRONT DESK | | | 3/12/2009 | | DONE |
|
|
|
Approved redlined plans available at front counter
|
Plan resubmittals received | | | 3/5/2009 | | |
Stephanie L. Cobbley
|
|
|
|
Issue and Print Permit | | | 12/8/2008 | | DONE |
|
|
|
|
Alarm Plan Check | | | 11/28/2008 | | FAIL |
|
|
|
see review comments and redlined plans
|
PLANS/APPL TAKEN TO FRONT DESK | | | 11/28/2008 | | DONE |
|
|
|
Denied plans available at front counter for contractor pick-up
|
Miscellaneous action | | | 11/28/2008 | | DONE |
|
|
|
Faxed review comments to contractor
|
Application received | | | 11/17/2008 | | |
|
|
|
|
Plan assigned to (Stephanie) | 11/17/2008 | | 11/17/2008 | | DONE |
Stephanie L. Cobbley
|
|
|
|