Permit Information
Permit NumberFIR08-00787
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 3896 N WOODY LN
Project NameIntermountain Property Dev
Customer Number 
ePlanReview 
Description
The Fire Sprinkler Scope of work consists of installing a 13D fire protection for a Live/Work unit.

Associated building permit BLD08-00224 (live/work unit 25) To construct a 2,000 sq.ft., two story, Live/Work unit (Townhouse) on a zero lot line. The First story includes a 756 sq.ft. non-residential use, operated by the tenant and shall comply with section 419 of the 2007 International Building Code Supplement. The first story also has a 36 sq.ft. covered porch, a 89 sq.ft. covered patio, and a 464 sq.ft. attached two car garage. A maximum of five non-residential workers or employees are allowed to occupy the non-residential area at any one time. The second story includes a 1,244 sq.ft., two bedroom, two bathroom, dwelling unit with a 89 sq.ft. balcony. The dwelling unit shall comply with the 2006 International Residential Code for a Single family townhouse dwelling. This building shall conform to section 903.3.1.3 of the 2006 IBC. An automatic sprinkler system shall be installed throughout in accordance with NFPA 13D. Any and all NFPA 13D systems shall be equipped with an alarm initiating device commonly referred to as a flow switch, and an outside alarm indicating device. A Fire Sprinkler Permit is required prior to beginning any fire sprinkler work. "This lot is within a Floodplain area. An elevation certificate is required to be submitted to and approved by Jim Wyllie, Public Works Department, prior to calling for a framing inspection." All work per the approved plans, engineering, plan review report, and alternate agreements on file. DRH07-00466, DRH08-00126, and CUP07-00121 per Planning and Zoning. **SRZ**

System Design History
This is a new fire protection system design per (IRC 2007 Supplement for Live/Work Unit) that references NFPA 13d.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection4/27/20094/28/20094/28/2009PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection4/23/20094/27/20094/27/2009PCANC
DetailsForrest France
Overbooked
INSP-Sprinkler Rough-in3/4/20093/4/20093/4/2009PPASS
DetailsTroy Cobbley
Per Tim Frost the deficiencies have been corrected and the sprinkler piping can be covered.
CHANGE STATUS TO (ISS)  3/4/2009 DONE
(F) Reprint permit  3/4/2009 DONE
Plan assigned to (Tim)2/26/2009 3/3/2009 PASS
DetailsTim Frost
Sprinkler Plan Check3/3/2009 3/3/2009 PASS
DetailsTim Frost
Please, see attached comments.
There are annotations on the plans.
PLANS/APPL TAKEN TO FRONT DESK  3/3/2009 DONE
DetailsTim Frost
Inspection Record Card- Fire3/3/2009 3/3/2009 DONE
Details
Telephone call  3/3/2009 DONE
Details
t/c w cameron hess at ###-#### - resubmittal ready
Permit Ready to Issue  3/3/2009 DONE
Details
Plan resubmittals received  2/26/2009  
DetailsTim Frost
Plan Modification: Recieved application, three copies of submittal package, and sheet FP1 of 1; taken to Fire Review
INSP-Sprinkler Rough-in/Hydro2/25/20092/25/20092/25/2009PFAIL
DetailsTroy Cobbley
One additional head required above the stairway for proper coverage.
1" install on the second floor when the plan indicates 1 1/4"
Main shifted approximately 5' on the second floor. Shifting the mains affected the hydraulic most remote area.
One head was leaking and was being replaced on the second floor.
Resubmittal of plans is required. Tim Frost
Override - Parcel Holds  12/10/2008  
Override - Parcel Holds  12/10/2008  
Issue and Print Permit  12/10/2008 DONE
Telephone call  12/9/2008 DONE
Details
t/c w cameron hess at ###-#### - permit ready and fees given
Override - Parcel Holds  12/9/2008  
Override - Parcel Holds  12/9/2008  
Permit Ready to Issue  12/9/2008 DONE
Sprinkler Plan Check  12/5/2008 PASS
Approved with annotations and comments
PLANS/APPL TAKEN TO FRONT DESK  12/5/2008 DONE
Telephone call  12/5/2008 DONE
Told contractor that the plans were approved however, they had to make sure that the heads were no closer than 8' apart in the coffee room to prevent cold sodering.
Override - Parcel Holds  12/5/2008  
Override - Parcel Holds  12/5/2008  
Inspection Record Card- Fire12/5/2008 12/5/2008 DONE
DetailsCathy Brown
Application received  11/24/2008  
Pending Assignment by SAM11/24/2008 11/24/2008 DONE
DetailsTim Frost