Information based on query as of Friday, July 5, 2024.
Permit Information
Permit NumberFIR08-00788
StatusFinaled
Name SIMPLEX GRINNELL
Site Address 333 N SAILFISH PL
Project NameBOISE CITY HALL WEST
Customer Number 
ePlanReview 
Description
This fire alarm permit is to add, remove and/or relocate notification and initiating devices to accommodate an addition and remodel to the existing building. New notification panels are being added.
NOTE: There are some existing devices shown to remain as-is. These devices were installed under the 2003 IFC, therefore must be verified that they meet visual spacing requirements of NFPA 72 edition 2002.

Associated building permit: BLD08-01321 (BOISE CITY HALL WEST) (CUP07-00107 and DRH08-00125) This building is fire sprinklered for unlimited area. To remodel an existing 92,040 square foot building (92,360 square feet after the addition) to be used as a satellite facility of Boise City Hall. The building will include a police station with office areas, a crime lab, a workout area, locker rooms, meeting rooms, an armory, and detention cells. There will also be Fire Department offices, Information Technology staff and equipment, and a community auditorium and lobby. Work is to include a 320 square foot entry vestibule addition, an awning, 2 restrooms accessible to the disabled, interior nonbearing walls, suspended acoustical ceilings, suspended gypsum board ceilings, gypsum board soffits, folding partitions, and interior finishes. The vestibule addition will include concrete footings, concrete foundations, concrete slab on grade, a 16 inch thick concrete exterior wall, steel stud exterior bearing and/or shear walls with wood structural panels, steal joist roof system with steel decking, and a membrane roof covering. The work is required to comply with the approved drawings, with the plan review report, and with all applicable codes and ordinances. The fire sprinkler system is required to comply with NFPA 13 as regulated by the Fire Department. **CJW**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection3/5/20093/6/20093/6/2009APASS
DetailsTroy Cobbley
permit finaled
INSP-Final Inspection3/4/20093/5/20093/5/2009AFAIL
DetailsTroy Cobbley
The strobes in the BreakRoom and the Mens Locker Room did not work. The strobes in Corridor 138C did not sync. The strobes in the Women's locker room need to be sync'd or a hydraulic closer installed on the door as discussed. The fire/smoke dampers need inspected.
INSP-Final Inspection3/3/20093/4/20093/4/2009AFAIL
DetailsTroy Cobbley
Contractor was not ready for inspection.
Issue and Print Permit  12/10/2008 DONE
Inspection Record Card- Fire12/9/2008 12/9/2008 DONE
Details
Telephone call  12/9/2008 DONE
Details
left message w angelia (w answering service) for charlie bayne at ###-#### - permit ready and fees given
Permit Ready to Issue  12/9/2008 DONE
Details
Alarm Plan Check  12/8/2008 PASS
See review comments and redlined plans
PLANS/APPL TAKEN TO FRONT DESK  12/8/2008 DONE
Application received  11/25/2008  
Plan assigned to (Stephanie)11/25/2008 11/25/2008 DONE
DetailsStephanie L. Cobbley