INSP-Final Inspection | 1/16/2009 | 1/16/2009 | 1/16/2009 | P | PASS |
Forrest France
|
|
|
Fire sprinkler permit finaled.
|
INSP-Sprinkler Rough-in | 12/22/2008 | 12/23/2008 | 12/23/2008 | A | PART |
Forrest France
|
|
|
Fire sprinkler system modification okay for cover.
|
Sprinkler Plan Check | 12/15/2008 | | 12/15/2008 | | PASS |
Scott Arellano
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 12/15/2008 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 12/15/2008 | | 12/15/2008 | | DONE |
Cathy Brown
|
|
|
|
Telephone call | | | 12/15/2008 | | |
Cathy Brown
|
|
|
tlk to jeff anderson ###-#### that permit and fees are ready to be picked up
|
Permit Ready to Issue | | | 12/15/2008 | | DONE |
Cathy Brown
|
|
|
|
Issue and Print Permit | | | 12/15/2008 | | DONE |
|
|
|
|
Application received | | | 12/12/2008 | | |
|
|
|
|
Pending Assignment by SAM | 12/12/2008 | | | | |
|
|
|
|