INSP-Final Inspection | 5/12/2009 | 5/12/2009 | 5/13/2009 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled. I spoke to the fire sprinkler contractor about some newly installed curtain tracks that have the potential to block the pendant sprinkler coverage. This would have the potential to hold up the live safety inspection sign off.
|
INSP-Sprinkler Rough-in/Hydro | 4/9/2009 | 4/9/2009 | 4/9/2009 | P | PASS |
Troy Cobbley
|
|
|
The overhead hydro test passed.
|
INSP-Sprinkler Rough-in/Hydro | 4/7/2009 | 4/9/2009 | 4/9/2009 | A | PART |
Troy Cobbley
|
|
|
The overhead hydro test failed but the overhead sprinkler piping can be covered. The overhead hydro is set back up for this afternoon.
|
Plan assigned to (Tim) | 2/12/2009 | | 2/17/2009 | | PASS |
Tim Frost
|
|
|
|
Sprinkler Plan Check | 2/17/2009 | | 2/17/2009 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
This review was for As Built plan changes
|
PLANS/APPL TAKEN TO FRONT DESK | | | 2/17/2009 | | DONE |
Tim Frost
|
|
|
|
Inspection Record Card- Fire | 2/17/2009 | | 2/17/2009 | | DONE |
|
|
|
|
Telephone call | | | 2/17/2009 | | DONE |
|
|
|
t/c w chris wilson at ###-#### - ready to be picked up - no fee (resubmittal)
|
Permit Ready to Issue | | | 2/17/2009 | | DONE |
|
|
|
|
CHANGE STATUS TO (ISS) | | | 2/17/2009 | | DONE |
|
|
|
|
(F) Reprint permit | | | 2/17/2009 | | DONE |
|
|
|
|
Telephone call | | | 2/13/2009 | | DONE |
|
|
|
Called Chris to ask him about the hydraulics. It appears that the below heads would have 270 GPM minimum and the above heads would have 296 minimum. If this is the case an additional set of hydraulics will be required to prove the above sprinklers will work with the available water supply. I am waiting for Chris at Treasure Valley Fire Protection to return my call.
|
Plan resubmittals received | | | 2/12/2009 | | |
Tim Frost
|
|
|
Rec'd plan mod- one copy of app and three copies of plans- taken to fire review
|
INSP-Sprinkler Rough-in | 2/10/2009 | 2/11/2009 | 2/11/2009 | A | PASS |
Troy Cobbley
|
|
|
Rough-in inspection passed. See the city approved plans for locations of corrections needed. The hard lid areas are ok to cover.
|
Issue and Print Permit | | | 1/2/2009 | | DONE |
|
|
|
|
Sprinkler Plan Check | 12/31/2008 | | 12/31/2008 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
There ARE annotations on the plans.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 12/31/2008 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 12/31/2008 | | 12/31/2008 | | DONE |
Cathy Brown
|
|
|
|
Telephone call | | | 12/31/2008 | | DONE |
Cathy Brown
|
|
|
lft vm with christopher wilson ###-#### that permit and fees are ready to be picked up
|
Permit Ready to Issue | | | 12/31/2008 | | DONE |
Cathy Brown
|
|
|
|
Plan resubmittals received | | | 12/29/2008 | | |
|
|
|
|
Telephone call | | | 12/22/2008 | | DONE |
|
|
|
left vm for chris wilson at ###-#### - can pick up permit - it was denied and needs to be resubmitted
|
Sprinkler Plan Check | 12/22/2008 | | 12/22/2008 | | FAIL |
Tim Frost
|
|
|
See attached review. No comments on plans
|
Application received | | | 12/16/2008 | | |
|
|
|
|
Pending Assignment by SAM | 12/16/2008 | | 12/16/2008 | | DONE |
Tim Frost
|
|
|
|
Case Summary | | | 12/16/2008 | | DONE |
|
|
|
|