Permit Information
Permit NumberFIR09-00002
StatusFinaled
Name ALLIED GENERAL FIRE & SECURITY
Site Address 3501 W ELDER ST
Project NameUNA MAS BLDG-ASSURANT HEALTH
Customer Number 
ePlanReview 
Description
This fire alarm permit is to add new notification devices to an existing fire alarm system to accommodate a tenant improvement. No initiating devices are part of this permit scope.

Associated building permit: BLD08-02567 (ASSURANT HEALTH) New 10,203 sq. ft. office space in an existing vacant shell space on the third floor of a 3 story building, with basement per approved plans. NOTE: This building is fully fire sprinklered for one-hour substitution. Work includes installation of interior non-bearing walls to create (13) private offices, (2) open office areas, (1) conference room, (1) Training room, (1) Breakroom, (1) File/Copy room, Millwork, installation of a suspended ceiling grid system, and miscellaneous finishes. Work also includes HVAC, Plumbing and Electrical. Common core restrooms & drinking fountains are located on each level W/ common service sink on third level, all part of Shell /Core permit (BLD06-00688). There is an existing central core to this building, approximately 780 sq. ft., which includes the three exit stair systems; and an elevator for accessibility compliance. Any modifications to the fire sprinkler system is required to comply with NFPA 13 as regulated by the Fire Department. All work per the approved plans, Engineering, and Plan Review report. **SRZ**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  5/11/2009 DONE
Plans taken to records to scan
INSP-Final Inspection3/23/20093/24/20093/24/2009APASS
DetailsForrest France
Items on correction notice field verified for completion, final walkthrough passed, permit finaled.
INSP-Final Inspection3/20/20093/23/20093/23/2009AFAIL
DetailsForrest France
Functional alarm testing not completed due to incorrect cd settings at two devices and one overspaced notification appliance at the open office area NW corner- locations marked on plans.
Issue and Print Permit  1/8/2009 DONE
Alarm Plan Check  1/7/2009 PASS
See review comments
PLANS/APPL TAKEN TO FRONT DESK  1/7/2009 DONE
Inspection Record Card- Fire1/7/2009 1/7/2009 DONE
Details
Telephone call  1/7/2009 DONE
Details
t/c w ken webster at ###-#### - permit ready and fees given
Permit Ready to Issue  1/7/2009 DONE
Details
Application received  1/5/2009 DONE