Miscellaneous action | | | 5/11/2009 | | DONE |
|
|
|
Plans taken to records to scan
|
INSP-Final Inspection | 4/24/2009 | 4/28/2009 | 4/28/2009 | A | PASS |
Forrest France
|
|
|
Items on correction notice have been repaired and passed final inspection, knox box installed, record of completion recieved, permit finaled.
|
INSP-Final Inspection | 2/25/2009 | 2/26/2009 | 2/26/2009 | P | FAIL |
Troy Cobbley
|
|
|
The smoke detectors are overspace in relation to the draft stopd and beams. Additional smoke detectors or spacing modifications are required. Provide verification of max. CFM of the existing HVAC units. See IMC 606 for duct smoke detector requirements. Provide testing of the audio/visual devices. Provide as-builts. Provide strobe coverage to meet the 16'-0" requirement fo review note #25 for residential requirements.
|
Telephone call | | | 2/11/2009 | | DONE |
|
|
|
I spoke with Ken Webster, Allied General (###-####), who indicated the system has been installed by Deacon Electric, but there are a few problems with the FACP to be resolved. They anticipate it will be ready for final inspection by Friday 2/13 or Monday 2/16.
|
Issue and Print Permit | | | 2/9/2009 | | DONE |
Barbara Stitt
|
|
|
|
Plan assigned to (Stephanie) | 1/27/2009 | | 2/6/2009 | | DONE |
Stephanie L. Cobbley
|
|
|
|
Alarm Plan Check | 2/6/2009 | | 2/6/2009 | | PASS |
Stephanie L. Cobbley
|
|
|
2nd Review (1st review had no comments). See review comments and redlined plans.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 2/6/2009 | | DONE |
|
|
|
Approved plans available at front counter for contractor pick-up
|
Inspection Record Card- Fire | 2/6/2009 | | 2/6/2009 | | DONE |
Rita DeYoung
|
|
|
|
Permit Ready to Issue | | | 2/6/2009 | | DONE |
Rita DeYoung
|
|
|
|
Telephone call | | | 2/6/2009 | | DONE |
Cathy Brown
|
|
|
lft vm with nick schafer ###-#### that permit and fees are ready to be picked up
|
Plan resubmittals received | | | 1/27/2009 | | |
Stephanie L. Cobbley
|
|
|
received application, three copies of Fire Alarm Data Sheets, three copies of plan sheets FA-0.0, FA-1.0, FA-2.0; taken to fire review
|
Alarm Plan Check | | | 1/27/2009 | | FAIL |
|
|
|
Plans failed due to sleeping area notification device issues. No written comments or redlined drawings.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 1/27/2009 | | DEFR |
|
|
|
no plans or comments to be picked up
|
Telephone call | | | 1/27/2009 | | DONE |
|
|
|
A phone call was made to the contractor regarding the sleep area notification devices. The candela listed is not appropriate for this application. The contractor stated he would resubit all plans and documentation. No review comments or redlined plans were done.
|
Application received | | | 1/14/2009 | | |
|
|
|
|
Plan assigned to (Stephanie) | 1/14/2009 | | 1/14/2009 | | DONE |
Stephanie L. Cobbley
|
|
|
|