Case Summary | | | 4/19/2010 | | DONE |
|
|
|
|
INSP-Final Inspection | 4/23/2009 | 4/24/2009 | 4/24/2009 | A | PASS |
Forrest France
|
|
|
Fire sprinkler permit work passed final inspection, preaction system supervision tested okay, permit finaled.
|
INSP-Sprinkler Rough-in/Hydro | 4/7/2009 | 4/7/2009 | 4/7/2009 | P | PASS |
Troy Cobbley
|
|
|
The above ground hydro test passed. The first test this morning failed but this afternoons test passed.
|
INSP-Sprinkler Rough-in/Hydro | 4/6/2009 | 4/7/2009 | 4/7/2009 | A | PASS |
Troy Cobbley
|
|
|
The 24 hour air test passed.
|
INSP-Sprinkler Rough-in/Hydro | 4/6/2009 | 4/6/2009 | 4/6/2009 | P | PART |
Troy Cobbley
|
|
|
24 hour air test started at 8:30 with 51psi on the guage.
|
INSP-Sprinkler Rough-in | 2/18/2009 | 2/18/2009 | 2/18/2009 | P | PASS |
Troy Cobbley
|
|
|
The rough-in inspection passed. Another rough-in inspection will be needed when the pendants have actually been placed in the t-bar grid which has not been installed yet. There is a pipe size descrepancy at the base of the new pre-action riser that needs clarified prior to final.
|
Sprinkler Plan Check | 1/29/2009 | | 1/29/2009 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
There are annotations on the plans. The existing remote area was changed to 982 sf. by the designer. The hydraulics on the existing remote area was not required since it was a 1-1 replacement situation.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 1/29/2009 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 1/29/2009 | | 1/29/2009 | | DONE |
Cathy Brown
|
|
|
|
Telephone call | | | 1/29/2009 | | DONE |
Cathy Brown
|
|
|
tlk to jeff anderson ###-#### that permit and fees are ready to be picked up
|
Permit Ready to Issue | | | 1/29/2009 | | DONE |
Cathy Brown
|
|
|
|
Issue and Print Permit | | | 1/29/2009 | | DONE |
Alexandra L. DeYoung
|
|
|
|
Plan resubmittals received | | | 1/27/2009 | | DONE |
|
|
|
Received 1 application and 3 sets of plans taken to fire
|
Sprinkler Plan Check | 1/22/2009 | | 1/22/2009 | | FAIL |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans
|
Miscellaneous action | | | 1/22/2009 | | DONE |
|
|
|
Emailed review comments to Jeff Anderson
|
Application received | | | 1/20/2009 | | |
|
|
|
|
Pending Assignment by SAM | 1/20/2009 | | 1/20/2009 | | DONE |
Tim Frost
|
|
|
|