INSP-Final Inspection | 3/13/2009 | 3/13/2009 | 3/13/2009 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Sprinkler Rough-in/Hydro | 3/13/2009 | 3/13/2009 | 3/13/2009 | P | PASS |
Troy Cobbley
|
|
|
permit finaled
|
INSP-Sprinkler Rough-in/Hydro | 3/11/2009 | 3/11/2009 | 3/11/2009 | P | FAIL |
Troy Cobbley
|
|
|
Sprinkler coverage is lacking in one area as shown on the approved plans. Also there are atleast three locations where new/relocated pendants are piped from the same 1" outlet which is not allowed as per review comment #5. Verify that the existing sprinkler system is current with its annual inspection.
|
Issue and Print Permit | | | 1/30/2009 | | DONE |
Tisha Gallop
|
|
|
|
Sprinkler Plan Check | 1/29/2009 | | 1/29/2009 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
There ARE annotations on the plans.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 1/29/2009 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 1/29/2009 | | 1/29/2009 | | DONE |
Cathy Brown
|
|
|
|
Telephone call | | | 1/29/2009 | | DONE |
Cathy Brown
|
|
|
tlk to brook ###-#### that permit and fees are ready to be picked up
|
Permit Ready to Issue | | | 1/29/2009 | | DONE |
|
|
|
|
Application received | | | 1/26/2009 | | |
|
|
|
|
Pending Assignment by SAM | 1/26/2009 | | 1/26/2009 | | DONE |
Tim Frost
|
|
|
|