Miscellaneous action | | | 6/15/2011 | | DONE |
|
|
|
Drawings taken to records for scanning.
|
INSP-Final Inspection | 2/17/2011 | 2/17/2011 | 2/17/2011 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Final Inspection | 2/15/2011 | 2/15/2011 | 2/15/2011 | P | FAIL |
Troy Cobbley
|
|
|
The tamper switches tested ok but came in on the same zone the the map indicated that the duct smoke detectors were on. So we tested two of the four duct smoke detectors and found that they havent been connected to the FACP. The duct detectors need to be connected to the FACP and the map corrected.
|
INSP-Final Inspection | 2/14/2011 | 2/15/2011 | 2/15/2011 | A | CANC |
Troy Cobbley
|
|
|
I called Bryan at ###-#### twice before going to the project and once after I arrived at the project but did not contact him. I left messages. No inspection was performed.
|
INSP-Final Inspection | 2/4/2011 | 2/7/2011 | 2/7/2011 | A | FAIL |
Troy Cobbley
|
|
|
Three tamper switches need to be adjusted. This includes two in the valve pit and one on the jockey pump.
|
INSP-Final Inspection | 2/2/2011 | 2/3/2011 | 2/3/2011 | P | CANC |
Troy Cobbley
|
|
|
Cancelled due to time constraints with micron plan review and inspection work load. Also per Guy, the fire sprinkler contractor needed to get setup for the phase reversal and loss of power signals. Will probably be rescheduled for next week.
|
CHANGE STATUS TO (ISS) | | | 12/27/2010 | | DONE |
|
|
|
|
(F) Reprint permit | | | 12/27/2010 | | DONE |
|
|
|
|
Plan assigned to (Stephanie) | 12/23/2010 | | 12/23/2010 | | DONE |
Stephanie L. Cobbley
|
|
|
|
Alarm Plan Check | 12/23/2010 | | 12/23/2010 | | PASS |
Stephanie L. Cobbley
|
|
|
Plan mod #2 approved. see review comments
|
PLANS TAKEN FRONT DESK ALARM | | | 12/23/2010 | | DONE |
|
|
|
Plan modification #2 approved plans available at front counter.
|
Inspection Record Card- Fire | 12/23/2010 | | 12/23/2010 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 12/23/2010 | | DONE |
|
|
|
t/c w lori - permit (plan mod) ready and fees given
|
Permit Ready to Issue | | | 12/23/2010 | | DONE |
|
|
|
|
Plan resubmittals received | | | 12/20/2010 | | DONE |
Christina Prado
|
|
|
Recieved 2 copies of application & checklist. Also Drawings F-1 & F-2 and site plan information;routed to fire review
|
Issue and Print Permit | | | 11/30/2010 | | DONE |
|
|
|
|
Alarm Plan Check | 11/29/2010 | | 11/29/2010 | | PASS |
Stephanie L. Cobbley
|
|
|
Plan modifications approved
|
PLANS TAKEN FRONT DESK ALARM | | | 11/29/2010 | | DONE |
|
|
|
Approved plan modification plans available at front counter
|
Inspection Record Card- Fire | 11/29/2010 | | 11/29/2010 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 11/29/2010 | | DONE |
|
|
|
t/c w lori - permit (plan mod) ready and fees given
|
Permit Ready to Issue | | | 11/29/2010 | | DONE |
|
|
|
|
Plan assigned to (Stephanie) | 11/22/2010 | | 11/29/2010 | | DONE |
Stephanie L. Cobbley
|
|
|
|
Telephone call | | | 11/24/2010 | | DONE |
|
|
|
Left Alarmco a message letting them know that the plan modifications did not contain any of the AES information in the submittal packets and that this would need to be either faxed or emailed over before I can approve the plans.
|
Plan resubmittals received | | | 11/22/2010 | | DONE |
Tisha Gallop
|
|
|
Plan modification: received two copies of application, submittal documents and plan; routed to fire review
|
INSP-Final Inspection | 11/15/2010 | 11/15/2010 | 11/15/2010 | P | FAIL |
Troy Cobbley
|
|
|
After arriving on site it was determined that this permit will be postponed due to a plan modification being performed to include additional fire alarm work.
|
Miscellaneous action | | | 11/15/2010 | | DONE |
|
|
|
After discussions with Lori, a plan modification will be submitted prior to calling for a final inspection to include relocating the AES and the FACP, tie in connections from a new fire pump, and ensure all existing sprinkler devices are tied in to the existing panel.
|
FIR-Aging Inspection | 10/27/2010 | 10/27/2010 | 10/28/2010 | | NR |
Troy Cobbley
|
|
|
Work is in progress. Per Guy all of these AES inspections are being called in shortly.
|
FIR-Aging Inspection | 6/22/2010 | 6/22/2010 | 6/22/2010 | | FAIL |
Forrest France
|
|
|
See inspection activity 1/26/10.
|
INSP-Final Inspection | 1/25/2010 | 1/26/2010 | 1/26/2010 | A | FAIL |
Forrest France
|
|
|
Need to provide verification that tamper switches at the pit backflow shutoff valves #1 and 2 are connected to the panel- as FLP wire is disconnected and exposed at a junction box labeled "pit valve os&y" in the riser room. Also need to retest alarm signals as the manual pull station failed to report.
|
INSP-Final Inspection | 12/8/2009 | 12/9/2009 | 12/9/2009 | P | CANC |
Troy Cobbley
|
|
|
Cancelled per Guy. To be rescheduled.
|
FIR-Aging Inspection | 6/23/2009 | 6/23/2009 | 6/23/2009 | | NR |
Troy Cobbley
|
|
|
work is in progress
|
Issue and Print Permit | | | 2/10/2009 | | DONE |
|
|
|
|
Plan assigned to (Stephanie) | 1/28/2009 | | 2/9/2009 | | DONE |
Stephanie L. Cobbley
|
|
|
|
Alarm Plan Check | 2/9/2009 | | 2/9/2009 | | PASS |
Stephanie L. Cobbley
|
|
|
see review comments
|
PLANS/APPL TAKEN TO FRONT DESK | | | 2/9/2009 | | DONE |
|
|
|
approved plans available at front counter
|
Inspection Record Card- Fire | 2/9/2009 | | 2/9/2009 | | DONE |
|
|
|
|
Telephone call | | | 2/9/2009 | | DONE |
|
|
|
t/c w lori at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 2/9/2009 | | DONE |
|
|
|
|
Application received | | | 1/28/2009 | | |
|
|
|
|