INSP-Final Inspection | 2/7/2011 | 2/8/2011 | 2/8/2011 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
Miscellaneous action | | | 2/8/2011 | | DONE |
|
|
|
Plans taken to records for scanning.
|
INSP-Final Inspection | 2/2/2011 | 2/3/2011 | 2/3/2011 | P | FAIL |
Troy Cobbley
|
|
|
All signals are ok except the trouble signals are not being sent out from the AES but restore signals are being sent out on the intella tap. It appears the wiring between the AES and the FACP may be suspect.
|
INSP-Final Inspection | 2/1/2011 | 2/2/2011 | 2/2/2011 | P | CANC |
Troy Cobbley
|
|
|
Please call Guy at ###-#### with inspection time. Phone #: ###-#### >> Inspection requested via web by Lori Brungardt Inspection cancelled from web by: Lori Brungardt
|
INSP-Final Inspection | 1/31/2011 | 2/1/2011 | 2/1/2011 | P | FAIL |
Troy Cobbley
|
|
|
The flow switch signal made it to the monitoring station but did not show up on Guys computer. The tamper switch is out of adjustment. After we left the building and started another inspection across the parking lot supervisory signals were coming in from this job. Basically this inspection will need to be redone.
|
CHANGE STATUS TO (ISS) | | | 1/27/2011 | | DONE |
Tisha Gallop
|
|
|
picked up approved plan mod
|
Plan assigned to (Stephanie) | 1/18/2011 | | 1/26/2011 | | DONE |
Stephanie L. Cobbley
|
|
|
|
Alarm Plan Check | 1/26/2011 | | 1/26/2011 | | PASS |
Stephanie L. Cobbley
|
|
|
Plan modification approved.
|
PLANS TAKEN FRONT DESK ALARM | | | 1/26/2011 | | DONE |
|
|
|
Approve plan modification plans available at front counter.
|
Inspection Record Card- Fire | 1/26/2011 | | 1/26/2011 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 1/26/2011 | | DONE |
|
|
|
t/c w lori - permit (plan mod) ready and fees given
|
Permit Ready to Issue | | | 1/26/2011 | | DONE |
|
|
|
|
Plan resubmittals received | | | 1/18/2011 | | DONE |
Tisha Gallop
|
|
|
Plan modification: received application and submittal folder; routed to Fire plan review.
|
FIR-Aging Inspection | 10/28/2010 | 10/28/2010 | 10/28/2010 | | NR |
Troy Cobbley
|
|
|
Work is in progress. Per Guy all of these AES inspections are being called in shortly.
|
FIR-Aging Inspection | 7/7/2010 | 7/7/2010 | 7/7/2010 | | NR |
Troy Cobbley
|
|
|
Per Bill the AES inspection scheduling is being addressed.
|
FIR-Aging Inspection | 5/21/2009 | 5/21/2009 | 5/21/2009 | | NR |
Troy Cobbley
|
|
|
Work is in progress
|
Alarm Plan Check | 2/17/2009 | | 2/17/2009 | | PASS |
Stephanie L. Cobbley
|
|
|
see written comments
|
PLANS/APPL TAKEN TO FRONT DESK | | | 2/17/2009 | | DONE |
|
|
|
approved plans available at front counter
|
Inspection Record Card- Fire | 2/17/2009 | | 2/17/2009 | | DONE |
|
|
|
|
Telephone call | | | 2/17/2009 | | DONE |
|
|
|
t/c w lori at ###-####- permit ready and fees given
|
Permit Ready to Issue | | | 2/17/2009 | | DONE |
|
|
|
|
Issue and Print Permit | | | 2/17/2009 | | DONE |
|
|
|
|
Application received | | | 1/28/2009 | | |
|
|
|
|