Permit Information
Permit NumberFIR09-00097
StatusFinaled
Name BIG M ELECTRIC INC
Site Address 4890 N CLOVERDALE RD
Project NameBoise Retirement Residence-A
Customer Number 
ePlanReview 
Description
BLDG A PLAN MODIFICATION 10-19-09:
This plan modification is to provide information on the atrium shutters, includes providing modules for synchronizing the audibility between the room notification devices and the building notification devices, as well as to implement as-built devices and previous plan review comments.

10/6/09 PLAN MODIFICATION: This plan modification is intended to include information on the atrium shutters as well as as-built information.
FAIL: Not all as-built information has been incorporated into the plans. Contractor (Mike Pemberton of Big M Electric) has been notified via telephone that a resubmittal is required to incorporate additional smoke detectors in the atrium planters as well as implementing all changes due to job site revisions as well as previous review comments.

This fire alarm permit is to provide a new fire alarm system in a new building. Permit scope includes automatic smoke detection system with full notification, monitoring for HVAC, dampers, and sprinkler system, Elevator recall functions, smoke shutters in the 3rd floor atrium, fire doors, a fire pump, kitchen hood suppression system monitoring, and an emergency generator.

Associated building permit: BLD08-02083 (BOISE RETIREMENT RESIDENCE - BLDG A - CENTER SECTION) To construct a new 26 unit (plus manager & co-manager units) 37,512 square foot, three story, I-1, non state licensed, residential care, assisted living assisted living facility, where all residence will be capable of responding to an emergency situation without physical assistance. This building will contain the supporting occupancies such as assembly areas, dining area, associated kitchen, and an atrium all per approved plans. This building to be fully fire sprinklered with an NPFA 13 system for area increase and the atrium area. This building section is separated from the west end (Section C) and the east end (Section B) by 2-hr. fire walls. Note: This project was reviewed by ICC for energy, structural, nonstructural and accessibility requirements for code compliance. (25 units are less than 800 sq.ft. and 3 units are more than 800 sq.ft.)
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  10/26/2009 DONE
Fire alarm plans taken to records
INSP-Final Inspection10/20/200910/20/200910/20/2009PPASS
DetailsTroy Cobbley
The syncing of the handicap rooms a/v's has been addressed. The placement and testing of the atrium smoke detectors has been addressed. Permit finaled.
Plan assigned to (Stephanie)10/15/2009 10/19/2009 DONE
DetailsStephanie L. Cobbley
10/19/2009 15:46:28 SLC - activity updated through activity FIRA24 from case FIR09-00097.
Alarm Plan Check10/19/2009 10/19/2009 PASS
DetailsStephanie L. Cobbley
Plan modification passed.
PLANS TAKEN FRONT DESK ALARM  10/19/2009 DONE
Approved plan modification drawings available at front counter
Inspection Record Card- Fire10/19/2009 10/19/2009 DONE
Details
Telephone call  10/19/2009 DONE
Details
t/c w bryan colson at ###-#### - permit (plan mod) ready and fees given
Permit Ready to Issue  10/19/2009 DONE
Details
CHANGE STATUS TO (ISS)  10/19/2009 DONE
(F) Reprint permit  10/19/2009 DONE
Plan resubmittals received  10/15/2009  
DetailsBarbara Stitt
INSP-Alarm Testing10/9/200910/9/200910/9/2009APASS
DetailsTroy Cobbley
The sync issue between the common area a/v's and the handi-cap room a/v's has been resolved and tested ok. Waiting on the resubmittals showing this work and the resolution with the atrium.
Telephone call  10/6/2009 DONE
Spoke with Michael Dillon (Dillon Consulting Engineers) who prepared the Smoke Management System Engineering Report. I referenced page 5 of the report, specifically the fourth paragraph detailing the planters and associated protection requirements. He clarified that he did, in fact, intend 30" planter width to mean 'width' and not 'length', as in, extend a minimum of 30" into the atrium area. He also clarified that the smoke detectors and sprinkler heads specified in his report as being needed in the planters are definately required due to the issues described in his report. SUMMARY: The planters are required to extend a minimum of 30" into the atrium; sprinklers and smoke detectors are required in those planters as specified in the report.
Telephone call  10/6/2009 DONE
Spoke withMichael Pemberton of Big M Electric regarding the plan modifications submitted on 10/2/09. The title block indicates 'as-built', however there are multiple items from previous reviews that were not addressed as well as the atrium smoke shutter documentation. I explained to him that I spoke with the engineer (see additional phone call activity) and verified that smoke detectors will need to be added to the planters specified in the smoke control report dated November 20, 2007. I gave him two options: 1) I will cross out the 'as-built' description on the plans, soley review them based on the shutter additions, and then he would need to submit again prior to calling for a final inspection with all of the changes incorporated into the drawings, thus paying any additional plan review fees; or 2) I can fail these submitted drawings and he can resubmit prior to calling for a final inspection will all changes incorporated that reflect the true as-built information including but not limited to the shutter information, additional smoke detectors in the atrium planters, room changes, previous review comments, etc..) thus paying only one set of review fees. He opted for the second option.
1st review completed  10/6/2009 DONE
Alarm Plan Check10/6/2009 10/6/2009 FAIL
DetailsStephanie L. Cobbley
Drawings are intended to be as-built, however do not reflect all as-built information (see phone call activities for further information). The contractor is aware that a resubmittal is required.
Plan resubmittals received  10/2/2009  
DetailsTisha Gallop
Plan Modification: received one copy of application and checklist, three copies of submittal documents and full set of plans; taken to fire review
INSP-Alarm Testing10/1/200910/1/200910/1/2009PPASS
DetailsTroy Cobbley
All of the smoke alarms were tested today as well as all of the fire sprinkler to fire alarm panel interconnections. There are two items left that need addressed. They are the shutters on the third floor atrium and the non-syncing of the horn/strobes in the first floor common areas and the handi-cap rooms.
INSP-Final Inspection9/29/20099/30/20099/30/2009AFAIL
DetailsTroy Cobbley
The smoke duct detectors for hvac shutdown and the fire/smoke dampers passed inspection today. Also the hood suppression system interconnection passed inspection. The 14ga wire has been installed at the NAC panels as well.
INSP-Final Inspection9/28/20099/29/20099/29/2009AFAIL
DetailsTroy Cobbley
The inspection continued today. Items left to test include the hood suppression system, hvac shutdown, EOL voltage drop, smoke alarms, smoke shutters/atrium smoke detectors and sprinkler system interconnections. Notification and initiating (smoke detectors/pull stations) were tested on all floors. Two were repaired while I waited.
INSP-Final Inspection9/25/20099/28/20099/28/2009AFAIL
DetailsTroy Cobbley
See the city approved plans for the initiating devices tested today as marked in red. The phone lines and supervision of the NAC panels were verified. One 16ga wire needs to be changed to 14ga as discussed and atrium smoke shutter sequence of operation needs to be verified since it has not been programmed per the approved drawings.
INSP-Alarm Testing7/6/20097/7/20097/7/2009APASS
DetailsTroy Cobbley
The rough-in inspection for the riser room is passed.
INSP-Alarm Testing7/1/20097/1/20097/1/2009PPASS
DetailsTroy Cobbley
The fire alarm rough-in for the first floor passed.
INSP-Alarm Testing6/24/20096/24/20096/24/2009PPASS
DetailsTroy Cobbley
The fire alarm rough-in for the second floor passed. One smoke detector appears to be overspaced from the east fire doors and will be verified at the final.
Telephone call  6/23/2009 DONE
The contractor called regarding smoke detector placement questions. The area in question is on sheet FA1.1.1 Dining 168. Apparently, there is a beam that is 18" deep that runs East-to-West. The ceiling height is 17.9'. Per NFPA 72, if the beam depth does not exceed 10% of the ceiling height, then it can be treated as a smooth ceiling, otherwise smoke detectors will need to be added to cover the 'pocket' created by the beam. In addtion, the contractor stated that there are dormers around the fireplace that did exceed the 10%. I indicated that based on his description that smoke detectors would need to be placed in the 'pocket' created by the dormers.
INSP-Alarm Testing6/9/20096/9/20096/10/2009PDONE
DetailsTroy Cobbley
This was a rough-in inspection for the center building third floor fire alarm system which passed.
INSP-Alarm Testing4/8/20094/8/20094/9/2009PCANC
DetailsTroy Cobbley
The wrong inspection number was called in.
INSP-Sprinkler Rough-in4/6/20094/6/20094/7/2009PCANC
DetailsTroy Cobbley
wrong permit called in.
Issue and Print Permit  3/9/2009  
DetailsBarbara Stitt
Plan assigned to (Stephanie)2/26/2009 3/5/2009 DONE
DetailsStephanie L. Cobbley
Alarm Plan Check3/5/2009 3/5/2009 PASS
DetailsStephanie L. Cobbley
See redlined plans and review comments
PLANS/APPL TAKEN TO FRONT DESK  3/5/2009 DONE
Approved redlined plans available at front counter
Inspection Record Card- Fire3/5/2009 3/5/2009 DONE
Details
Telephone call  3/5/2009 DONE
Details
t/c w michael pemberton at ###-#### - permit ready and no fees due
Permit Ready to Issue  3/5/2009 DONE
Details
Plan resubmittals received  2/26/2009  
DetailsStephanie L. Cobbley
received application, letter from Curry Architecture, product info, plan sheets A1.1, FA0, FA0.1, FA0.2, FA0.3, FA1.1, FA1.1.1, FA1.1.2, FA1.1.3, FA1.2, FA1.2.1, FA1.2.2, FA1.2.3, FA2.1, FA2.1.1, FA2.1.2, FA2.1.3, FA2.2, FA2.2.1, FA2.2.2, FA2.2.3, FA3.1, FA3.1.1, FA3.1.2, FA3.1.3, FA3.2, FA3.2.1, FA3.2.2, FA3.2.3, FA4, FA5, FA6.1, FA6.2, FA7; taken to Fire Review
Plan assigned to (Stephanie)1/28/2009 2/12/2009 DONE
DetailsStephanie L. Cobbley
Alarm Plan Check2/12/2009 2/11/2009 FAIL
DetailsStephanie L. Cobbley
see review comments and redlined plans
PLANS/APPL TAKEN TO FRONT DESK  2/11/2009 DONE
denied plans available for pick up
Miscellaneous action  2/11/2009 DONE
faxed comments to contractor
Application received  1/28/2009