Miscellaneous action | | | 12/21/2010 | | DONE |
|
|
|
Plans taken to records for scanning.
|
INSP-Final Inspection | 12/6/2010 | 12/6/2010 | 12/6/2010 | P | PASS |
Troy Cobbley
|
|
|
permit finaled
|
INSP-Final Inspection | 12/1/2010 | 12/2/2010 | 12/2/2010 | A | FAIL |
Troy Cobbley
|
|
|
The interior tamper switches now function. We could not find a key for the lock on the PIV to verify that it had been repaired as needed per the previous inspection.
|
INSP-Final Inspection | 12/1/2010 | 12/1/2010 | 12/1/2010 | P | CANC |
Troy Cobbley
|
|
|
Cancelled due to time constraints. Rich is going to have Lori reschedule it for tomorrow morning.
|
FIR-Aging Inspection | 10/28/2010 | 10/28/2010 | 10/28/2010 | | NR |
Troy Cobbley
|
|
|
Work is in progress. Per Guy all of these AES inspections are being called in shortly.
|
FIR-Aging Inspection | 7/20/2010 | 7/20/2010 | 7/20/2010 | | NR |
Troy Cobbley
|
|
|
Per Bill the scheduling is being addressed.
|
INSP-Final Inspection | 4/5/2010 | 4/5/2010 | 4/5/2010 | P | FAIL |
Troy Cobbley
|
|
|
The panel had a Netcon 5. All signals were sent but "east PIV" kept coming in as a trouble signal on the annuciator and when the other tamper switches were activated "east tamper" supervisory stayed stuck on the annuciator even after being reset at the main facp and the annunciator.
|
INSP-Sprinkler Rough-in/Hydro | 4/5/2010 | 4/5/2010 | 4/5/2010 | P | CANC |
Troy Cobbley
|
|
|
please call ###-#### with time Inspection requested from web by: Lori Brungardt Phone #: ###-#### Inspection cancelled from web by: Lori Brungardt
|
INSP-Final Inspection | 4/2/2010 | 4/5/2010 | 4/5/2010 | A | CANC |
Troy Cobbley
|
|
|
Inspection canceled after repeated attempts to contact. I left message. No inspection performed.
|
FIR-Aging Inspection | 5/29/2009 | 5/29/2009 | 5/29/2009 | | NR |
Troy Cobbley
|
|
|
work is in progress
|
Issue and Print Permit | | | 2/25/2009 | | |
|
|
|
|
Plan assigned to (Stephanie) | 2/4/2009 | | 2/17/2009 | | DONE |
Stephanie L. Cobbley
|
|
|
|
Alarm Plan Check | 2/17/2009 | | 2/17/2009 | | PASS |
Stephanie L. Cobbley
|
|
|
see review comments
|
PLANS/APPL TAKEN TO FRONT DESK | | | 2/17/2009 | | DONE |
|
|
|
approved plans available at front counter
|
Inspection Record Card- Fire | 2/17/2009 | | 2/17/2009 | | DONE |
|
|
|
|
Telephone call | | | 2/17/2009 | | DONE |
|
|
|
t/c w lori at ###-#### - permit ready and fees due
|
Permit Ready to Issue | | | 2/17/2009 | | DONE |
|
|
|
|
Application received | | | 2/4/2009 | | |
|
|
|
|