Miscellaneous action | | | 5/11/2009 | | DONE |
|
|
|
Plans taken to records to scan
|
INSP-Final Inspection | 3/26/2009 | 3/27/2009 | 3/27/2009 | A | PASS |
Troy Cobbley
|
|
|
permit finaled
|
INSP-Final Inspection | 3/25/2009 | 3/26/2009 | 3/26/2009 | P | FAIL |
Troy Cobbley
|
|
|
The duct smoke detector located over the office area is mounted incorrectly which has been verified with FireX technical support. An updated map is also required at the facp. The plans also indicated existing duct smoke detectors in other tenant spaces. These detectors are not connected to the existing fire alarm panel as required by the IMC. I contacted Mark Senteno with the fire dept. via email about this issue.
|
INSP-Conference | 3/25/2009 | 3/25/2009 | 3/25/2009 | P | PASS |
Troy Cobbley
|
|
|
Scotty wanted to know if a record of completion would be required for this project. For this small scope of work I would not need them.
|
Issue and Print Permit | | | 2/20/2009 | | DONE |
|
|
|
|
Plan assigned to (Stephanie) | 2/6/2009 | | 2/18/2009 | | DONE |
Stephanie L. Cobbley
|
|
|
|
Alarm Plan Check | 2/18/2009 | | 2/18/2009 | | PASS |
Stephanie L. Cobbley
|
|
|
see review comments
|
PLANS/APPL TAKEN TO FRONT DESK | | | 2/18/2009 | | DONE |
|
|
|
Approved plans available at front counter
|
Inspection Record Card- Fire | 2/18/2009 | | 2/18/2009 | | DONE |
|
|
|
|
Telephone call | | | 2/18/2009 | | DONE |
|
|
|
t/c w dave at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 2/18/2009 | | DONE |
|
|
|
|
Case Summary | | | 2/6/2009 | | DONE |
|
|
|
|
Application received | | | 2/6/2009 | | |
|
|
|
|