Information based on query as of Wednesday, July 17, 2024.
Permit Information
Permit NumberFIR09-00127
StatusFinaled
Name COMMERCIAL FIRE PROTECTION
Site Address 833 W DIAMOND ST
Project NameECCO ELECTRONICS
Customer Number 
ePlanReview 
Description
The Fire Sprinkler Scope of work consists of adding a new preaction system for the data room.

(ECCO) Remodel to a portion of the existing 40,335 square foot first floor and a first time tenant improvement to the 9,230 square foot second floor. NOTE: This building is fully fire sprinklered for area increase. Work to the first floor to include: Adding new elevator, elevator equipment room constructed of 8" concrete smooth surface block on the exterior of the building , new Concore 2500 Access floor panel system in the server room, extending the existing server room walls to the underside of the second floor, construction of new walls for a lab area with a new door/tempered window, construction of new walls for a break room, and other misc. work per the plans. Work to the second floor to include: Construction of new walls for a new conference room, offices, mail room, smaller conference room, corridor with a breakroom/coffee station, one men's restroom, one women's restroom, one unisex restroom, and second floor framing construction for new HVAC and janitor/storage rooms. Second floor misc. work to include: New glass handrail, relocating a ducting chase, modifying the vestibule ceiling, sloping gypcrete flooring down to plywood floor landings at both stairs, and adding office cubicles. All work per approved plans, Engineering, attached Plan review report, and CZC08-00167. **SRZ**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/6/20095/6/20095/6/2009APASS
DetailsForrest France
Fire sprinkler permit work passed final inspection, alarm interconnections tested okay.
INSP-Sprinkler Rough-in/Hydro4/27/20094/28/20094/28/2009PPART
DetailsForrest France
Pressure testing for the new preaction system completed okay, per NFPA 13 pneumatic testing for the single interlock system is not required.
INSP-Sprinkler Rough-in/Hydro4/27/20094/27/20094/27/2009PPART
DetailsForrest France
Begin air testing at 3:00 pm @ 41.5 psig.
INSP-Sprinkler Rough-in/Hydro4/27/20094/27/20094/27/2009APART
DetailsForrest France
OH hydrostatic retest of the preaction system passed.
INSP-Sprinkler Rough-in/Hydro4/23/20094/24/20094/24/2009PFAIL
DetailsForrest France
Hydrostatic test for the new preaction system failed due to pressure loss at the guage per site inspection completed by T. Frost.
Pending Assignment by SAM2/13/2009 4/21/2009 DONE
DetailsAlexandra L. DeYoung
4/21/2009 15:23:28 ALR - activity updated through activity FIRA158 from case FIR09-00259.
INSP-Sprinkler Rough-in/Hydro4/17/20094/17/20094/17/2009PNR
DetailsForrest France
INSP-Sprinkler Rough-in3/20/20093/20/20093/20/2009PFAIL
DetailsForrest France
See inspection comments per T. Frost.
Issue and Print Permit  2/25/2009 DONE
DetailsBarbara Stitt
Sprinkler Plan Check2/20/2009 2/20/2009 PASS
DetailsTim Frost
Please, see attached comments.
There are NO annotations on the plans.
There ARE review comments that require field verification.
PLANS/APPL TAKEN TO FRONT DESK  2/20/2009 DONE
DetailsTim Frost
Inspection Record Card- Fire2/20/2009 2/20/2009 DONE
Details
Telephone call  2/20/2009 DONE
Details
t/c w john at ###-#### - permit ready and fees given
Permit Ready to Issue  2/20/2009 DONE
Details
Application received  2/13/2009  
Case Summary  2/13/2009 DONE