INSP-Final Inspection | 5/6/2009 | 5/6/2009 | 5/6/2009 | A | PASS |
Forrest France
|
|
|
Fire sprinkler permit work passed final inspection, alarm interconnections tested okay.
|
INSP-Sprinkler Rough-in/Hydro | 4/27/2009 | 4/28/2009 | 4/28/2009 | P | PART |
Forrest France
|
|
|
Pressure testing for the new preaction system completed okay, per NFPA 13 pneumatic testing for the single interlock system is not required.
|
INSP-Sprinkler Rough-in/Hydro | 4/27/2009 | 4/27/2009 | 4/27/2009 | P | PART |
Forrest France
|
|
|
Begin air testing at 3:00 pm @ 41.5 psig.
|
INSP-Sprinkler Rough-in/Hydro | 4/27/2009 | 4/27/2009 | 4/27/2009 | A | PART |
Forrest France
|
|
|
OH hydrostatic retest of the preaction system passed.
|
INSP-Sprinkler Rough-in/Hydro | 4/23/2009 | 4/24/2009 | 4/24/2009 | P | FAIL |
Forrest France
|
|
|
Hydrostatic test for the new preaction system failed due to pressure loss at the guage per site inspection completed by T. Frost.
|
Pending Assignment by SAM | 2/13/2009 | | 4/21/2009 | | DONE |
Alexandra L. DeYoung
|
|
|
4/21/2009 15:23:28 ALR - activity updated through activity FIRA158 from case FIR09-00259.
|
INSP-Sprinkler Rough-in/Hydro | 4/17/2009 | 4/17/2009 | 4/17/2009 | P | NR |
Forrest France
|
|
|
|
INSP-Sprinkler Rough-in | 3/20/2009 | 3/20/2009 | 3/20/2009 | P | FAIL |
Forrest France
|
|
|
See inspection comments per T. Frost.
|
Issue and Print Permit | | | 2/25/2009 | | DONE |
Barbara Stitt
|
|
|
|
Sprinkler Plan Check | 2/20/2009 | | 2/20/2009 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
There ARE review comments that require field verification.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 2/20/2009 | | DONE |
Tim Frost
|
|
|
|
Inspection Record Card- Fire | 2/20/2009 | | 2/20/2009 | | DONE |
|
|
|
|
Telephone call | | | 2/20/2009 | | DONE |
|
|
|
t/c w john at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 2/20/2009 | | DONE |
|
|
|
|
Application received | | | 2/13/2009 | | |
|
|
|
|
Case Summary | | | 2/13/2009 | | DONE |
|
|
|
|