Permit Information
Permit NumberFIR09-00131
StatusFinaled
Name MOUNTAIN ALARM
Site Address 8601 W EMERALD 140
Project NameEmerald Park Building 1
Customer Number 
ePlanReview 
Description
This quick permit scope is to relocate 3 exisitng manual pull stations and remount 2 indicating lights for existing duct detectors due to demolitions during a remodel. No notification or any new devices are part of this permit scope. NOTE TO INSPECTOR: It has been discussed that the pull station on the south door needs to be mounted further than the normally allowed 5' from the door. Per the contractor this is due to the addition of glass where the original pull station was located. Location on the nearest wall closest to the door is approved in this case, provided it still complies with mounting height requirements of the current code. No other written coments. Associated building permit: BLD08-02385 (**VANILLA FINISH** - Emerald Park Building 1 - Suite #140) Permit to remodel an existing 7,738 square foot office space. Space will be used for offices and accessory uses. This use is defined as a B occupancy. Work to include: demolition of interior nonbearing walls, construction of interior non-bearing walls to enclose a conference room and a utility room, installation of new doors and hardware as indicated on plans, installation of a new hi/low drinking fountain, installation of a new mop sink, installation of new electrical, and installation of interior finishes in compliance with chapter 8 of the IBC. This building is fully fire sprinklered any alterations or modifications to the sprinkler system WILL REQUIRE A SEPARATE PERMIT and shall be installed per NFPA #13 as regulated by the fire department. **TLW**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  5/11/2009 DONE
Plans taken to records to scan
INSP-Final Inspection3/30/20093/30/20093/30/2009PPASS
DetailsTroy Cobbley
life safety passed.
INSP-Final Inspection3/11/20093/11/20093/11/2009PCANC
DetailsTroy Cobbley
Per the mechanical contractor the damper motors are burned out and will need replaced. The inspection will be called in for next week.
INSP-Final Inspection3/10/20093/11/20093/11/2009AFAIL
DetailsTroy Cobbley
The existing fire/smoke dampers did not function. They are currently in the closed state and appear to be stuck. All other items passed.
Issue and Print Permit  2/26/2009 DONE
Plan assigned to (Stephanie)2/18/2009 2/25/2009 DONE
DetailsStephanie L. Cobbley
Alarm Plan Check2/25/2009 2/25/2009 PASS
DetailsStephanie L. Cobbley
Quick permit approved, no written comments
PLANS/APPL TAKEN TO FRONT DESK  2/25/2009 DONE
Approved plans available at front counter
Miscellaneous action  2/25/2009 DONE
The contractor noted that the pull station on the south door is located outside the 5' distance allowed by NFPA 72. The contractor stated that the remodel replaced a portion of the wall with glass, placing the pull station approximately 8' from the door. After discussing this with Sam, it was agreed that due to the situation, that the new location for the pull station would be appropriate as long as it still meets mounting height requirements of current code.
Inspection Record Card- Fire2/25/2009 2/25/2009 DONE
Details
Telephone call  2/25/2009 DONE
Details
left vm for bret anderson at ###-#### - permit rady and fees given
Permit Ready to Issue  2/25/2009 DONE
Details
Application received  2/18/2009