Permit Information
Permit NumberFIR09-00137
StatusFinaled
Name SIMPLEX GRINNELL
Site Address 800 W IDAHO ST Unit: 200
Project NameComedy Club
Customer Number 
ePlanReview 
Description
The Fire Sprinkler Scope of work consists of adding new sprinklers, relocating and removing existing sprinklers to accommodate new wall configurations. All existing sprinklers will be replaces with quick response sprinklers. There is to be no ceiling through out the space. Sprinklers have been spaced around the HVAC to avoid obstruction issues. The existing system is a grid. One new branch line is being added and connected to an existing branch line.

(COMEDY CLUB TI) This building is fire sprinklered to substitute for 1-hr fire-resistive construction. To remodel a 5,016 square foot restaurant tenant space on the 2nd floor of the "Mode Building" for a new tenant. This space was formerly occupied by "Noodles Restaurant" and by "Dublin Up Irish Pub & Eatery". Work is to include: guardrails to the exterior of the SE sliding glass windows, interior nonbearing walls, floor coverings, a bar, a walk in cooler (stick framed with fiberglass insulation), new lighting, installation of operable partition wall, installation of interior finishes in accordance w/ Ch. 8 of the 2006 IBC, and furniture all per approved drawings, engineering, and plan review report on file. This building is fully fire sprinklered any alterations to the sprinkler system shall be maintained per NFPA #13 as regulated by the fire department. This tenant will not be serving food.**TLW**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Pending Assignment by SAM2/20/2009 4/16/2009 DONE
DetailsAlexandra L. DeYoung
4/16/2009 12:18:22 ALR - activity updated through activity FIRA158 from case FIR09-00245.
Telephone call  4/15/2009 DONE
DetailsTim Frost
Spoke with Brad at SimplexGrinnell in regards to the two new accordian doors. Since we have adequate protection on each side of the doors to cover the entire area, I did not see any problem with the potential for the new sprinklers inbetween the doors possible causing a cold soldering affect. The only time the new sprinklers in between the doors are required are when the doors are closed. When the doors are closed there will be no cold soldering affect.
INSP-Final Inspection4/1/20094/2/20094/2/2009PPASS
DetailsForrest France
Items on issued correction notice verified for completion, fire sprinkler permit finaled.
INSP-Sprinkler Rough-in3/16/20093/17/20093/17/2009PPART
DetailsForrest France
See plan annotations for locations of repairs to be made including two upright heads obstructed by adjacent ductwork, deficient existing seismic bracing at the 3" main within the scope of remodel area, dry pendent at the new cooler has not yet been installed. Remainder of overhead modifications okayed.
Sprinkler Plan Check2/24/2009 2/24/2009 PASS
DetailsTim Frost
Please, see attached comments.
There are NO annotations on the plans.
PLANS/APPL TAKEN TO FRONT DESK  2/24/2009 DONE
DetailsTim Frost
Inspection Record Card- Fire2/24/2009 2/24/2009 DONE
Details
Telephone call  2/24/2009 DONE
Details
t/c w brad at ###-#### - permit ready and fees given
Permit Ready to Issue  2/24/2009 DONE
Details
Issue and Print Permit  2/24/2009 DONE
Application received  2/20/2009  
Case Summary  2/20/2009 DONE