Miscellaneous action | | | 12/3/2009 | | DONE |
|
|
|
FA plans taken to records for scanning
|
INSP-Final Inspection | 11/24/2009 | 11/25/2009 | 11/25/2009 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled. The releasing system devices were spot checked for functionality.
|
Telephone call | | | 10/28/2009 | | DONE |
|
|
|
Joe from Allied General called and asked if they could email me a new data sheet for the AES panel installed (it is a different model from the original submittals). I let him know he could email it to me, but if there were any problems (i.e. compatibility, operational etc,) or conflicting information he would need to resubmit. I told him I would let him know either way.
|
Miscellaneous action | | | 10/28/2009 | | DONE |
|
|
|
Recieved an emailed data sheet from Joe at Allied general for and AES 7750F that will be the one used on this project. It is acceptable based on the information provided. No resubmittal is necessary for this particular issue. Subject to field approval. I emailed them back letting them know it was acceptable and to please provide the data sheet and installation manual to the inspector at time of inspection.
|
INSP-Final Inspection | 10/5/2009 | 10/7/2009 | 10/7/2009 | A | FAIL |
Troy Cobbley
|
|
|
The module monitoring trouble on the NAC panel has been provided and tested. The 18ah batteries are now added and both sets of approved plans are on site. The EOL voltage is passed on the circuit over the office area of the building. The inspection was stopped from sending additional signals due to the AES panel being at a Netcom 6. It temporarily went to a Netcom 5 but then went back to a 6. Also the sound from the horns on the notification circuit is not sync'd as required per NFPA 72 Chapter 6. Placement of the notification devices appeared to be ok except back in a storage room where the strobe was not placed as per the plan and now coverage is lacking. This device will need to be relocated or an additional device added.
|
INSP-Final Inspection | 9/24/2009 | 9/25/2009 | 9/25/2009 | A | CANC |
Troy Cobbley
|
|
|
Overbooked. Contacted David .
|
INSP-Final Inspection | 9/16/2009 | 9/21/2009 | 9/21/2009 | A | FAIL |
Troy Cobbley
|
|
|
No real inspection was started. The most up to date plans showing the plan modification/audio visuals was not on site. The batteries in the FACP are incorrect. Dave was going to cordinate with Treasure Valley Fire to test the alarm valve interconnection. The trouble monitor module located at the remote power supply has not been installed. No other items have been tested or inspected.
|
FIR-Aging Inspection | 6/12/2009 | 6/12/2009 | 6/12/2009 | | NR |
Troy Cobbley
|
|
|
Work in progress
|
Inspection Record Card- Fire | 6/8/2009 | | 6/8/2009 | | DONE |
Barbara Stitt
|
|
|
|
Telephone call | | | 6/8/2009 | | DONE |
Barbara Stitt
|
|
|
Left voice message for Ken Webster that permit is ready & fees due 6-8-09 @ 8:41am BAS
|
(F) Reprint permit | | | 6/8/2009 | | DONE |
|
|
|
|
CHANGE STATUS TO (ISS) | | | 6/8/2009 | | DONE |
|
|
|
|
Plan assigned to (Stephanie) | 6/5/2009 | | 6/5/2009 | | DONE |
Stephanie L. Cobbley
|
|
|
6/5/2009 15:26:06 SLC - activity updated through activity FIRA24 from case FIR09-00150.
|
Plan resubmittals received | | | 6/5/2009 | | |
Stephanie L. Cobbley
|
|
|
Rec'd plan mod- two copies taken to Stephanie
|
Alarm Plan Check | 6/5/2009 | | 6/5/2009 | | PASS |
Stephanie L. Cobbley
|
|
|
See redlines and review comments. Plan modifications to supplement previously approved documents dated 3/11/09 (not replace)
|
PLANS TAKEN FRONT DESK ALARM | | | 6/5/2009 | | DONE |
|
|
|
Approved redlined plans available at front counter. Plan modification documents are to supplement (not replace) existing approved drawings dated 3/11/09.
|
Issue and Print Permit | | | 3/13/2009 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 3/12/2009 | | 3/12/2009 | | DONE |
|
|
|
|
Telephone call | | | 3/12/2009 | | DONE |
|
|
|
left vm for ken webster at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 3/12/2009 | | DONE |
|
|
|
|
Plan assigned to (Stephanie) | 2/26/2009 | | 3/11/2009 | | DONE |
Stephanie L. Cobbley
|
|
|
|
Alarm Plan Check | 3/11/2009 | | 3/11/2009 | | PASS |
Stephanie L. Cobbley
|
|
|
see review comments
|
PLANS/APPL TAKEN TO FRONT DESK | | | 3/11/2009 | | DONE |
|
|
|
Approved plans available at front counter
|
Application received | | | 2/26/2009 | | |
|
|
|
|