Miscellaneous action | | | 6/3/2009 | | DONE |
|
|
|
Taken to records for scanning
|
INSP-Final Inspection | 5/26/2009 | 5/27/2009 | 5/27/2009 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled. The originally submitted AES panel has installed now.
|
INSP-Final Inspection | 5/22/2009 | 5/26/2009 | 5/26/2009 | A | FAIL |
Troy Cobbley
|
|
|
I tried to do this inpsection twice today. The first time paper work was missing such as the Inspection and Testing form, the NetCom signal strenght verification and the building map was incorrect. When I returned the required paper work was there but I found that the AES wireless transmitter that was installed was not the model number that was submitted and approved. Also when we tried to send a trouble signal no was transmitted and when a tamper switch was operated a water flow signal was transmitted to central station. The inspection was stopped and will need to be rescheduled after the correct transmitter is installed or plan review is contacted and approves this different model. Also all signals need to be verified.
|
Plan assigned to (Stephanie) | 3/11/2009 | | 3/25/2009 | | DONE |
Stephanie L. Cobbley
|
|
|
3/25/2009 09:18:05 SLC - activity updated through activity FIRA24 from case FIR09-00168.
|
Alarm Plan Check | 3/25/2009 | | 3/25/2009 | | PASS |
Stephanie L. Cobbley
|
|
|
see review comments
|
PLANS TAKEN FRONT DESK ALARM | | | 3/25/2009 | | DONE |
|
|
|
Approved plans available at front counter
|
Inspection Record Card- Fire | 3/25/2009 | | 3/25/2009 | | DONE |
|
|
|
|
Telephone call | | | 3/25/2009 | | DONE |
|
|
|
t/c w ken webster at ###-#### - permit ready
|
Permit Ready to Issue | | | 3/25/2009 | | DONE |
|
|
|
|
Issue and Print Permit | | | 3/25/2009 | | DONE |
|
|
|
|
Application received | | | 3/11/2009 | | |
|
|
|
|