Miscellaneous action | | | 6/15/2011 | | DONE |
|
|
|
Drawings taken to records for scanning.
|
INSP-Final Inspection | 2/24/2011 | 2/24/2011 | 2/24/2011 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
(F) Reprint permit | | | 2/24/2011 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 2/24/2011 | | 2/24/2011 | | DONE |
Tisha Gallop
|
|
|
|
INSP-Final Inspection | 2/23/2011 | 2/23/2011 | 2/23/2011 | P | FAIL |
Troy Cobbley
|
|
|
The approved plans are missing so no actual inspection was performed. The netcon was now a 5.
|
INSP-Final Inspection | 2/18/2011 | 2/22/2011 | 2/23/2011 | A | DEFR |
Forrest France
|
|
|
Scheduled 2/23 PM.
|
INSP-Final Inspection | 2/17/2011 | 2/17/2011 | 2/17/2011 | P | FAIL |
Troy Cobbley
|
|
|
Cancelled due to time constraits.
|
FIR-Aging Inspection | 2/9/2011 | 2/9/2011 | 2/10/2011 | | NR |
Troy Cobbley
|
|
|
Per Bill these inspections are being addressed.
|
FIR-Aging Inspection | 11/16/2010 | 11/16/2010 | 11/16/2010 | | NR |
Troy Cobbley
|
|
|
work is in progress
|
INSP-Sprinkler Rough-in/Hydro | 4/1/2010 | 4/2/2010 | 4/2/2010 | P | FAIL |
Troy Cobbley
|
|
|
We verified the Netcon rating at the beginning of the inspection and found that it got only a 6. U.L. listing is for a 5 or less. No other items inspected.
|
Issue and Print Permit | | | 3/30/2010 | | DONE |
|
|
|
|
Miscellaneous action | | | 3/29/2010 | | DONE |
|
|
|
Requested documentation recieved from contractor
|
Alarm Plan Check | 3/29/2010 | | 3/29/2010 | | PASS |
Stephanie L. Cobbley
|
|
|
see review comments
|
PLANS TAKEN FRONT DESK ALARM | | | 3/29/2010 | | DONE |
|
|
|
approved plans available at front counter
|
Inspection Record Card- Fire | 3/29/2010 | | 3/29/2010 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 3/29/2010 | | DONE |
|
|
|
t/c w lori at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 3/29/2010 | | DONE |
|
|
|
|
Plan assigned to (Stephanie) | 3/16/2009 | | 3/29/2010 | | DONE |
Stephanie L. Cobbley
|
|
|
3/29/2010 14:12:41 SLC - activity updated through activity FIRA24 from case FIR09-00175.
|
Telephone call | | | 3/26/2010 | | DONE |
|
|
|
Let Alarmco know they still need to provide a pull station for this sprinkler monitoring panel, show it on the one-line, and to provide data sheets for the pull station and FACP, battery calculations, and an operations matrix. I let them know that I would not reject the plans if I could get the information by Monday (3/29/10) morning.
|
Plan resubmittals received | | | 3/23/2010 | | |
Barbara Stitt
|
|
|
|
Telephone call | | | 3/16/2010 | | DONE |
|
|
|
Spoke to Lori asking about the status of this project and that we are still waiting for resubmittals. She stated she would need to talk to Bill and would get back to me.
|
Miscellaneous action | | | 3/30/2009 | | DONE |
Tisha Gallop
|
|
|
picked up failed plans
|
1st review completed | | | 3/25/2009 | | FAIL |
Stephanie L. Cobbley
|
|
|
|
Alarm Plan Check | 3/25/2009 | | 3/25/2009 | | FAIL |
Stephanie L. Cobbley
|
|
|
see review comments. Denied plans available at front counter for pick up
|
Miscellaneous action | | | 3/25/2009 | | DONE |
|
|
|
faxed review comments to contractor
|
Telephone call | | | 3/24/2009 | | DONE |
|
|
|
Spoke with Laurie regarding the AES panel. Their plans indicate the AES is to be used as a stand alone sprinkler riser monitoring only panel. I let her know that this is not allowed. She stated she would have Alan contact me for further information.
|
Case Summary | | | 3/16/2009 | | DONE |
|
|
|
|