Permit NumberFIR09-00189
StatusFinaled
Name COMMERCIAL FIRE PROTECTION
Site Address 1709 W SPAULDING ST
Project NameSpaulding Residence
Customer Number 
ePlanReview 
Description
The Fire Sprinkler Scope of work consists of sprinklering an existing home that is being converted to assisted living facility per NFPA 13D. There is one floor. A new underground 1 ΒΌ" connection with backflow preventer is being supplied.

There is NO building permit associated with this project.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection7/20/20097/23/20097/23/2009PPASS
DetailsForrest France
Fire sprinkler permit work okayed for final status.
INSP-Sprinkler Rough-in6/29/20096/29/20096/29/2009PPART
DetailsForrest France
Need access to the west half of the attic space for tenting and insulation inspection.
INSP-Conference6/16/20096/16/20096/16/2009PDONE
DetailsForrest France
Regarding outside waterflow bell and existing fire alarm panel.
INSP-Sprinkler Rough-in/Hydro6/15/20096/15/20096/15/2009PPART
DetailsForrest France
Pending completion of tenting for cold cavity protection of wet system piping.
INSP-Supply line flush5/27/20095/28/20095/28/2009APART
DetailsForrest France
UG fire supply line flush witnessed acceptable.
INSP-Supply line flush5/21/20095/27/20095/27/2009PFAIL
DetailsForrest France
No water available for the underground flush, preliminary walkthrough for the overhead installation done, riser is not finished at this time.
Miscellaneous action  5/27/2009 DONE
DetailsTim Frost
Please, see attached email regarding UDG change of pipe type. The new UDG is approved since it is a larger diameter than the piping that was calculated.
INSP-Sprinkler Rough-in5/19/20095/20/20095/20/2009APART
DetailsTroy Cobbley
The underground piping installed is 1 1/4" cpvc. Per the approved plans, note #4, if the piping is not poly then resubmittals are required. I contacted bruce about this but gave him the ok to cover. It also appears that the underground supply is coming up closer to the exterior wall than what is shown on the plans. This too will need to be addressed.
Issue and Print Permit  4/9/2009 DONE
Plan assigned to (Tim)4/3/2009 4/6/2009 DONE
DetailsTim Frost
Sprinkler Plan Check4/6/2009 4/6/2009 PASS
DetailsTim Frost
Please, see attached comments.
There are NO annotations on the plans.
PLANS TAKEN FRONT DESK ALARM  4/6/2009 DONE
Inspection Record Card- Fire4/6/2009 4/6/2009 DONE
Details
Telephone call  4/6/2009 DONE
Details
left message with jen for brook at ###-#### - permit ready and fees given
Permit Ready to Issue  4/6/2009 DONE
Details
Pending Assignment by SAM4/1/2009 4/3/2009 DONE
DetailsDarla L Downs
4/3/2009 11:24:47 DLD - activity updated through activity FIRA158 from case FIR09-00189.
Application received  4/1/2009