Miscellaneous action | | | 1/6/2010 | | DONE |
|
|
|
Fire alarm plans taken to records for scanning.
|
INSP-Final Inspection | 12/14/2009 | 12/15/2009 | 12/15/2009 | P | PASS |
Forrest France
|
|
|
Corrections field verified, final inspection passed, fire alarm permit finaled.
|
INSP-Final Inspection | 12/10/2009 | 12/11/2009 | 12/11/2009 | A | PART |
Forrest France
|
|
|
Inspection passed with the exception of RTU 26 in need of repair, and RTU 1 without access to complete testing, list of signals dated 12/10 and 12/11 to be provided at next inspection and prior to final.
|
INSP-Final Inspection | 12/9/2009 | 12/9/2009 | 12/10/2009 | P | PART |
Forrest France
|
|
|
Partial testing of the relocated duct detector housings completed today, noted RTU 26 detector failed to report to the panel, manometer testing completed okay for the units tested.
|
FIR-Aging Inspection | 7/17/2009 | 7/17/2009 | 7/20/2009 | | DONE |
Forrest France
|
|
|
Pending site inspection request.
|
Alarm Plan Check | 4/17/2009 | | 4/17/2009 | | PASS |
Stephanie L. Cobbley
|
|
|
see review comments
|
PLANS TAKEN FRONT DESK ALARM | | | 4/17/2009 | | DONE |
|
|
|
Approved plans available at front counter
|
Permit Ready to Issue | | | 4/17/2009 | | DONE |
Alexandra L. DeYoung
|
|
|
|
Telephone call | | | 4/17/2009 | | DONE |
Alexandra L. DeYoung
|
|
|
LM for John- permit ready
|
Issue and Print Permit | | | 4/17/2009 | | DONE |
|
|
|
|
Plan assigned to (Stephanie) | 4/2/2009 | | 4/16/2009 | | DONE |
Stephanie L. Cobbley
|
|
|
4/16/2009 13:01:39 SLC - activity updated through activity FIRA24 from case FIR09-00192.
|
Case Summary | | | 4/2/2009 | | DONE |
|
|
|
|
Application received | | | 4/2/2009 | | |
|
|
|
|