Miscellaneous action | | | 10/1/2009 | | DONE |
|
|
|
Fire alarm plans taken to records for scanning
|
INSP-Final Inspection | 9/15/2009 | 9/21/2009 | 9/22/2009 | A | PASS |
Forrest France
|
|
|
Fire alarm work passed field testing, permit finaled.
|
Issue and Print Permit | | | 9/9/2009 | | |
|
|
|
|
Miscellaneous action | | | 5/1/2009 | | DONE |
|
|
|
roll of plans went out on site with issuance of Fir09-00208//ok per SLC
|
Plan assigned to (Stephanie) | 4/7/2009 | | 4/22/2009 | | DONE |
Stephanie L. Cobbley
|
|
|
4/22/2009 07:54:10 SLC - activity updated through activity FIRA24 from case FIR09-00221.
|
Inspection Record Card- Fire | 4/22/2009 | | 4/22/2009 | | DONE |
|
|
|
|
Telephone call | | | 4/22/2009 | | DONE |
|
|
|
t/c w phil at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 4/22/2009 | | DONE |
|
|
|
|
Alarm Plan Check | 4/21/2009 | | 4/21/2009 | | PASS |
Stephanie L. Cobbley
|
|
|
See review comments
|
PLANS TAKEN FRONT DESK ALARM | | | 4/21/2009 | | DONE |
|
|
|
Approved plans available at front counter
|
Application received | | | 4/7/2009 | | |
|
|
|
|