Miscellaneous action | | | 1/6/2010 | | DONE |
|
|
|
Fire alarm plans taken to records for scanning.
|
INSP-Final Inspection | 12/24/2009 | 12/24/2009 | 12/24/2009 | P | PASS |
Forrest France
|
|
|
Correction items verified for completion, remainder of fire alarm work tested satisfactory, inspection passed, permit finaled.
|
INSP-Final Inspection | 12/23/2009 | 12/23/2009 | 12/23/2009 | P | FAIL |
Forrest France
|
|
|
Overspaced notification appliances at two rooms, missing notification device at one room, duct detector sample and vent tubes must be installed per mfg. cut sheet, gate valves at the sprinkler riser incorrectly reported at offsite monitoring as trouble conditions, outside bell repaired while on site. FACP phone lines, battery trouble, SD and MP at the panel tested okay.
|
INSP-Final Inspection | 12/16/2009 | 12/18/2009 | 12/17/2009 | A | CANC |
Forrest France
|
|
|
Tom Phone #: ###-#### --cancelled by Joe/Allied General on 12/17/09 4:31pm
|
FIR-Aging Inspection | 7/23/2009 | 7/23/2009 | 7/23/2009 | | DONE |
Forrest France
|
|
|
Work in progress, site construction underway.
|
Plan assigned to (Stephanie) | 4/8/2009 | | 4/23/2009 | | DONE |
Stephanie L. Cobbley
|
|
|
4/23/2009 07:22:13 SLC - activity updated through activity FIRA24 from case FIR09-00233.
|
Alarm Plan Check | 4/23/2009 | | 4/23/2009 | | PASS |
Stephanie L. Cobbley
|
|
|
See review comments
|
PLANS TAKEN FRONT DESK ALARM | | | 4/23/2009 | | DONE |
|
|
|
Approved drawings available at front counter
|
Inspection Record Card- Fire | 4/23/2009 | | 4/23/2009 | | DONE |
|
|
|
|
Telephone call | | | 4/23/2009 | | DONE |
|
|
|
t/c w ken at ###-#### - permit ready and fees given - also past due fees
|
Permit Ready to Issue | | | 4/23/2009 | | DONE |
|
|
|
|
Issue and Print Permit | | | 4/23/2009 | | DONE |
Tisha Gallop
|
|
|
|
Application received | | | 4/8/2009 | | |
|
|
|
|