INSP-Final Inspection | 6/26/2009 | 6/29/2009 | 6/29/2009 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Final Inspection | 6/24/2009 | 6/26/2009 | 6/26/2009 | A | FAIL |
Troy Cobbley
|
|
|
Provide the required clearance around the underground stub-in supply riser. Forward flush passed. All other items are passed.
|
INSP-Sprinkler Rough-in/Hydro | 6/2/2009 | 6/3/2009 | 6/3/2009 | A | PASS |
Troy Cobbley
|
|
|
The overhead hydro test passed. All piping can be covered except the pipe just south of the main entrance due to insulation that is hanging from the roof deck acting as an obstruction to the attic sprinklers.
|
Miscellaneous action | | | 5/29/2009 | | DONE |
Tim Frost
|
|
|
Contractor changed the backflow preventer from a 3" to a 4". The manufacturer was the same Wilkings. The 4" has less friction loss than the 3". Therefore the change is APPROVED.
|
CHANGE STATUS TO (ISS) | | | 5/27/2009 | | DONE |
Alexandra L. DeYoung
|
|
|
|
(F) Reprint permit | | | 5/27/2009 | | DONE |
Alexandra L. DeYoung
|
|
|
|
Plan assigned to (Tim) | 5/15/2009 | | 5/19/2009 | | DONE |
Tim Frost
|
|
|
5/19/2009 14:14:18 TRF - activity updated through activity FIRA22 from case FIR09-00239.
|
Sprinkler Plan Check | 5/19/2009 | | 5/19/2009 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 5/19/2009 | | DONE |
Tim Frost
|
|
|
|
Telephone call | | | 5/19/2009 | | DONE |
|
|
|
t/c w bryan at ###-#### - permit (plan mod) ready and fees given
|
Permit Ready to Issue | | | 5/19/2009 | | DONE |
|
|
|
|
Plan resubmittals received | | | 5/15/2009 | | |
Tisha Gallop
|
|
|
Plan Modification: Received four copies of application, submittal documents and plan sheet FP1; taken to fire review
|
INSP-Sprinkler Rough-in | 5/11/2009 | 5/12/2009 | 5/12/2009 | A | PASS |
Troy Cobbley
|
|
|
Todays inspection was for cover of the sprinkler piping above the mezzanine only.
|
INSP-Sprinkler Rough-in | 5/7/2009 | 5/7/2009 | 5/7/2009 | P | PASS |
Troy Cobbley
|
|
|
Sprinkler piping above the hard lid areas are okay to cover.
|
Plan assigned to (Tim) | 4/23/2009 | | 4/30/2009 | | DONE |
Tim Frost
|
|
|
4/30/2009 10:21:01 TRF - activity updated through activity FIRA22 from case FIR09-00239.
|
Sprinkler Plan Check | 4/30/2009 | | 4/30/2009 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 4/30/2009 | | DONE |
Tim Frost
|
|
|
|
Inspection Record Card- Fire | 4/30/2009 | | 4/30/2009 | | DONE |
|
|
|
|
Telephone call | | | 4/30/2009 | | DONE |
|
|
|
left message w darci for bryan at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 4/30/2009 | | DONE |
|
|
|
|
Issue and Print Permit | | | 4/30/2009 | | DONE |
|
|
|
|
Plan resubmittals received | | | 4/23/2009 | | |
Tisha Gallop
|
|
|
received four copies of application, submittal info and plan sheet FP1; taken to fire review
|
Case Summary | | | 4/22/2009 | | |
|
|
|
|
Early Start | | | 4/22/2009 | | DONE |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
Plan assigned to (Tim) | 4/9/2009 | | 4/21/2009 | | DONE |
Tim Frost
|
|
|
|
Sprinkler Plan Check | 4/21/2009 | | 4/21/2009 | | FAIL |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
Miscellaneous action | | | 4/21/2009 | | DONE |
Tim Frost
|
|
|
1st Review faxed
|
Telephone call | | | 4/21/2009 | | DONE |
|
|
|
t/c w ken at ###-#### - permit rejected - needs to be picked up and resubmitted
|
Application received | | | 4/9/2009 | | |
|
|
|
|