INSP-Final Inspection | 6/29/2009 | 6/30/2009 | 6/30/2009 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled. The forward flush passed.
|
INSP-Final Inspection | 6/29/2009 | 6/29/2009 | 6/29/2009 | P | FAIL |
Troy Cobbley
|
|
|
Sprinkler piping in the wash bay has been modified to match original approved plan. Forward flush failed.
|
INSP-Final Inspection | 6/23/2009 | 6/23/2009 | 6/23/2009 | P | FAIL |
Troy Cobbley
|
|
|
The plans do not reflect the additional sprinklers heads in the compressor room that have been added to the the anti-freeze system. Per my discussion with Tim Frost these changes need to be resubmitted due to the adjacent remote hydraulic area being effected by a non self closing door. Also two 45 fittings have been added at the base of the riser which are not shown on the plans. The backflow preventor needs to be certified and the forward flush performed.
|
Inspection Record Card- Fire | 6/23/2009 | | 6/23/2009 | | DONE |
|
|
|
|
Telephone call | | | 6/23/2009 | | DONE |
|
|
|
left message with thelma for brook at ###-#### - permit (plan mod) ready and fees given
|
Permit Ready to Issue | | | 6/23/2009 | | DONE |
|
|
|
|
CHANGE STATUS TO (ISS) | | | 6/23/2009 | | DONE |
Alexandra L. DeYoung
|
|
|
|
(F) Reprint permit | | | 6/23/2009 | | DONE |
Alexandra L. DeYoung
|
|
|
|
Plan assigned to (Tim) | 6/19/2009 | | 6/22/2009 | | DONE |
Tim Frost
|
|
|
6/22/2009 16:35:57 TRF - activity updated through activity FIRA22 from case FIR09-00247.
|
Sprinkler Plan Check | 6/22/2009 | | 6/22/2009 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 6/22/2009 | | DONE |
Tim Frost
|
|
|
|
Plan resubmittals received | | | 6/19/2009 | | |
Tisha Gallop
|
|
|
Received three copies of application, United Water Flow sheet, Hydraulic Calcs, submittal info packet and plan sheets FP-1, FP-2; taken to Fire Review
|
INSP-Sprinkler Rough-in/Hydro | 6/15/2009 | 6/15/2009 | 6/16/2009 | P | PASS |
Troy Cobbley
|
|
|
The overhead hydro test passed. The FDC piping was not included in the hydro test and will need to be done.
|
INSP-Sprinkler Rough-in/Hydro | 6/9/2009 | 6/10/2009 | 6/10/2009 | P | PART |
Troy Cobbley
|
|
|
Todays inspection was a rough-in. See the city approved plans for the corrections required which include an overspaced head, a pendant that needs to be supplied from its own mechanical tee, additional hangers on the 2" anti-freeze supply piping and resubmittals showing the anti-freeze system in the front entry canopy and the modifications at the wash bay.
|
Telephone call | | | 6/8/2009 | | DONE |
|
|
|
Spoke with Terry at Commerical Fire. He said that there would be (1) combustible beam in the outside canopy. I told him sprinklers would not be required due to the extremely limited amount of combustibles.
|
INSP-Sprinkler Rough-in/Hydro | 5/5/2009 | 5/6/2009 | 5/7/2009 | P | PART |
Troy Cobbley
|
|
|
The sprinkler piping above the office/lobby/storage areas are ok to cover
|
INSP-Sprinkler Rough-in | 5/4/2009 | 5/4/2009 | 5/4/2009 | P | PART |
Troy Cobbley
|
|
|
The rough-in inspection for the piping below the mezzanine passed. An additional inspection will be required when the ceilings and light fixtures have been installed.
|
Issue and Print Permit | | | 5/4/2009 | | DONE |
|
|
|
|
Plan assigned to (Tim) | 4/28/2009 | | 5/1/2009 | | DONE |
Tim Frost
|
|
|
5/1/2009 15:05:44 TRF - activity updated through activity FIRA22 from case FIR09-00247.
|
Sprinkler Plan Check | 5/1/2009 | | 5/1/2009 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 5/1/2009 | | DONE |
Tim Frost
|
|
|
|
Inspection Record Card- Fire | 5/1/2009 | | 5/1/2009 | | DONE |
|
|
|
|
Telephone call | | | 5/1/2009 | | DONE |
|
|
|
left message with leah for brook at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 5/1/2009 | | DONE |
|
|
|
|
Plan resubmittals received | | | 4/28/2009 | | |
Tim Frost
|
|
|
|
Miscellaneous action | | | 4/23/2009 | | DONE |
Tisha Gallop
|
|
|
picked up rejected plans
|
Telephone call | | | 4/22/2009 | | DONE |
|
|
|
t/c w brook at ###-#### - permit rejected - needs to be picked up and resubmitted
|
Plan assigned to (Tim) | 4/16/2009 | | 4/21/2009 | | DONE |
Tim Frost
|
|
|
Resubmittal
|
Sprinkler Plan Check | 4/21/2009 | | 4/21/2009 | | FAIL |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
Miscellaneous action | | | 4/21/2009 | | DONE |
|
|
|
Emailed comments to Brook
|
Application received | | | 4/16/2009 | | |
|
|
|
|
Pending Assignment by SAM | 4/16/2009 | | 4/16/2009 | | DONE |
Tisha Gallop
|
|
|
4/16/2009 14:35:26 LEG - activity updated through activity FIRA158 from case FIR09-00247.
|