Miscellaneous action | | | 1/5/2010 | | DONE |
Tim Frost
|
|
|
Plans taken to scanning.
|
INSP-Final Inspection | 11/18/2009 | 11/18/2009 | 11/18/2009 | P | PASS |
Forrest France
|
|
|
Fire sprinkler permit okayed for final status, corrections completed.
|
INSP-Final Inspection | 9/15/2009 | 9/16/2009 | 9/17/2009 | A | PART |
Forrest France
|
|
|
TOC approved.
|
INSP-Sprinkler Rough-in/Hydro | 9/8/2009 | 9/8/2009 | 9/8/2009 | P | PART |
Forrest France
|
|
|
Overhead hydrostatic testing passed, final pending project related fire alarm permit work, main drain valve does not need to be electricaly supervised, need "911" sign at the outside bell.
|
INSP-Sprinkler Rough-in/Hydro | 9/4/2009 | 9/4/2009 | 9/8/2009 | P | PART |
Forrest France
|
|
|
John Phone #: ###-####
|
INSP-Sprinkler Rough-in | 8/26/2009 | 8/26/2009 | 8/28/2009 | P | PART |
Forrest France
|
|
|
See inspection comments per site visit by T. Frost dated 8/26-Missing SW sprinklers below the garage doors if they are going to be roll back doors. Riser is not stacked. Roof top heater is blocking sprinkler discharge. Ceiling areas are OK to cover.
|
INSP-Sprinkler Rough-in | 7/29/2009 | 7/29/2009 | 7/29/2009 | P | PART |
Forrest France
|
|
|
Okay to cover hard lid ceilings at the mens and womens restrooms per red lines and initials on stamped plan set.
|
Plan assigned to (Tim) | 4/30/2009 | | 5/5/2009 | | DONE |
Tim Frost
|
|
|
5/5/2009 13:52:35 TRF - activity updated through activity FIRA22 from case FIR09-00260.
|
Sprinkler Plan Check | 5/5/2009 | | 5/5/2009 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 5/5/2009 | | DONE |
Tim Frost
|
|
|
|
Inspection Record Card- Fire | 5/5/2009 | | 5/5/2009 | | DONE |
|
|
|
|
Telephone call | | | 5/5/2009 | | DONE |
|
|
|
t/c w chris at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 5/5/2009 | | DONE |
|
|
|
|
Issue and Print Permit | | | 5/5/2009 | | DONE |
|
|
|
|
Plan resubmittals received | | | 4/30/2009 | | |
Tim Frost
|
|
|
|
Plan assigned to (Tim) | 4/30/2009 | | 4/30/2009 | | DONE |
Tim Frost
|
|
|
|
Plan assigned to (Tim) | 4/21/2009 | | 4/29/2009 | | DONE |
Tim Frost
|
|
|
New 05-05-09
|
Sprinkler Plan Check | 4/29/2009 | | 4/29/2009 | | FAIL |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
Telephone call | | | 4/29/2009 | | DONE |
|
|
|
t/c w chris at ###-#### - permit denied - needs to be picked up and resubmitted
|
Permit Ready to Issue | | | 4/29/2009 | | DONE |
|
|
|
|
Application received | | | 4/21/2009 | | |
|
|
|
|
Case Summary | | | 4/21/2009 | | DONE |
|
|
|
|