Miscellaneous action | | | 1/5/2010 | | DONE |
Tim Frost
|
|
|
Plans taken to scanning.
|
INSP-Final Inspection | 11/4/2009 | 11/5/2009 | 11/5/2009 | P | PASS |
Forrest France
|
|
|
On site functional trip testing of the new dry system completed satisfactory, water delivered to the inspectors test at 60 seconds. Final walkthrough passed, permit finaled.
|
INSP-Final Inspection | 10/20/2009 | 10/20/2009 | 10/21/2009 | P | NH |
Forrest France
|
|
|
Need the fire sprinkler contractor representative on site to complete functional trip testing of the new dry system valve and appurtenances.
|
INSP-Sprinkler Rough-in/Hydro | 6/22/2009 | 6/23/2009 | 6/23/2009 | A | PART |
Forrest France
|
|
|
Concluded satisfactory 24 hr. pneumatic testing with allowable pressure loss of 1/2 psi.
|
INSP-Sprinkler Rough-in/Hydro | 6/19/2009 | 6/22/2009 | 6/22/2009 | A | PART |
Forrest France
|
|
|
Begin 24 hr. air testing for the new dry system at 40.5 psig @ 10:00.
|
INSP-Sprinkler Rough-in/Hydro | 6/18/2009 | 6/19/2009 | 6/19/2009 | A | PART |
Forrest France
|
|
|
Overhead hydrostatic testing for the new dry system passed, also reinspected C/N items from previous visit.
|
INSP-Sprinkler Rough-in/Hydro | 6/18/2009 | 6/18/2009 | 6/18/2009 | P | FAIL |
Forrest France
|
|
|
Correction list includes blocked upright coverage at the equipment room, missing flexible couplings at the feed main through warehouse wall, provide listed air maintenance device, noted dry valve installed does not match type submitted, remote test connection has been relocated from where shown on approved plans.
|
Issue and Print Permit | | | 5/4/2009 | | DONE |
|
|
|
|
Plan assigned to (Tim) | 4/23/2009 | | 5/1/2009 | | DONE |
Tim Frost
|
|
|
5/1/2009 13:52:20 TRF - activity updated through activity FIRA22 from case FIR09-00264.
|
Sprinkler Plan Check | 5/1/2009 | | 5/1/2009 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 5/1/2009 | | DONE |
Tim Frost
|
|
|
|
Inspection Record Card- Fire | 5/1/2009 | | 5/1/2009 | | DONE |
|
|
|
|
Telephone call | | | 5/1/2009 | | DONE |
|
|
|
left message w bobbi for brook at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 5/1/2009 | | DONE |
|
|
|
|
Application received | | | 4/23/2009 | | |
|
|
|
|