Information based on query as of Wednesday, July 17, 2024.
Permit Information
Permit NumberFIR09-00282
StatusFinaled
Name PHOENIX FIRE PROTECTION
Site Address 516 W HALE ST
Project NameIconic Apartments - Bldg I
Customer Number 
ePlanReview 
Description
Fire Work Scope:

The Fire Sprinkler Scope of work consists of adding a new 13R sprinkler system to existing apartments. The project is divided into 5 permits to obtain separate occupancies; however, it is one building. This is the only review for all 5 permits. The permits are FIR09-00282 - FIR09-00286. The building permit numbers are BLD09-00017, BLD09-00508 - BLD08-00511

Plan Mod Scope:
The plans have been reviewed for the ballooned areas only. All other areas are to conform to original approved submittal. One above and below (522 A & B) unit is not being remodeled at this time. The sprinklers are located based on no walls. The piping in these units will be steel. When the unit is eventually finished the sprinklers will be required to be relocated. A new submittal will be required if it in the excess of 180 days; prior to that time, a plan mod may be submitted.

(Building I - 516 W. Hale St. units 100 & 200) **PLAN MODIFICATION 4/17/2009** This project is NOW to convert an existing two bedroom, one bathroom, two story apartment unit into (2) one bedroom, one bathroom units. Work to include: Minor demolition, new non-load bearing partitions, electrical modifications, paint and floor finishes, new automatic fire sprinkler system installed throughout in accordance with NFPA 13R, new bathroom (first floor unit), new kitchenette (second floor unit), and a sixteen square foot addition for the fire riser room will be added to the building. A phased upgrade agreement is approved and attached for the automatic sprinkler system improvements. All other alterations related to this building are permitted under BLD09-00508, and BLD09-00509, BLD09-00510, BLD09-00511. All work per approved plan modification plans and attached plan review report. The occupant load calculated under this permit is only for the units being remodeled/added. DRH08-00152, CUP08-00073, and CZC09-00047 per planning and zoning. **SRZ**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  3/8/2010 DONE
Plans sent to scanning.
Miscellaneous action  1/5/2010 DONE
DetailsTim Frost
Plans taken to scanning.
INSP-Final Inspection12/31/200912/31/200912/31/2009PPASS
DetailsForrest France
Fire sprinkler permit finaled.
INSP-Final Inspection12/28/200912/29/200912/29/2009APART
DetailsForrest France
Correction notice items completed, final pending satisfactory alarm permit final for system supervision.
INSP-Final Inspection12/15/200912/16/200912/16/2009ANR
DetailsForrest France
Phone #: ###-#### Internet Inspection Request from: Scott Carter II
INSP-Final Inspection12/11/200912/15/200912/15/2009ANR
DetailsForrest France
Noted one SW head at the first floor mechanical closet in need of adjustment, provide "911" sign at the outside bell, project related FIR permits 09-00283 thru 286 are "ready to issue", need escutcheons installed and travel caps removed at units 518,520, and 524, noted heat has been provided and sheetrock ceilings in the shell unit are done, riser supervision to be tested in conjunction with fire alarm permit work re-inspect.
(F) Reprint permit  11/13/2009 DONE
CHANGE STATUS TO (ISS)  11/13/2009 DONE
Sprinkler Plan Check11/4/2009 11/4/2009 PASS
DetailsTim Frost
Please, see attached comments.
There are NO annotations on the plans.
1st review completed  11/4/2009 DONE
DetailsTim Frost
PLANS/APPL TAKEN TO FRONT DESK  11/4/2009 DONE
DetailsTim Frost
Telephone call  11/4/2009 DONE
Details
left message w michelle for trent at ###-#### - permit (plan mod) ready and fees given
Permit Ready to Issue  11/4/2009 DONE
Details
INSP-Sprinkler Rough-in/Hydro10/15/200910/16/200910/16/2009PFAIL
DetailsTroy Cobbley
Hydro test failed. This is just a preliminary hydro since not all of the sprinkler system has been installed.
INSP-Sprinkler Rough-in/Hydro10/14/200910/15/200910/15/2009APASS
DetailsTroy Cobbley
Sprinkler piping is ok to cove in units 105 and 205. Resubmittal are needed since the pipe sizing and routing have changed and feeds the remote area. I have marked the "as installed" size and routing on the city approved plans. I let the sprinkler fitter know that If ceilings and piping need to be removed due to the resubmittal plans that is the burden of the contractor.
INSP-Sprinkler Rough-in/Hydro10/13/200910/14/200910/14/2009ACANC
DetailsTroy Cobbley
Overbooked. I spoke to the contact to have them reschedule for tomorrow.
INSP-Sprinkler Rough-in7/27/20097/27/20097/27/2009PPART
DetailsForrest France
Approved overhead cover for unit 101 and 201east side 516.
INSP-Sprinkler Rough-in5/19/20095/19/20095/19/2009PPASS
DetailsTroy Cobbley
The 2" underground supply piping is ok to cover. The contractor did not have the original approved plans, just copies, on site. I let him know those would be needed at the next inspection.
Plan assigned to (Tim)5/1/2009 5/5/2009 DONE
DetailsTim Frost
5/5/2009 08:41:22 TRF - activity updated through activity FIRA22 from case FIR09-00282.
Sprinkler Plan Check5/5/2009 5/5/2009 PASS
DetailsTim Frost
Please, see attached comments.
There are NO annotations on the plans.
PLANS/APPL TAKEN TO FRONT DESK  5/5/2009 DONE
DetailsTim Frost
Override - Parcel Holds  5/5/2009  
Override - Parcel Holds  5/5/2009  
Inspection Record Card- Fire5/5/2009 5/5/2009 DONE
Details
Telephone call  5/5/2009 DONE
Details
left message w michelle for trent at ###-#### - permit ready and fees given
Override - Parcel Holds  5/5/2009  
Override - Parcel Holds  5/5/2009  
Permit Ready to Issue  5/5/2009 DONE
Details
Override - Parcel Holds  5/5/2009  
Override - Parcel Holds  5/5/2009  
Issue and Print Permit  5/5/2009 DONE
Application received  5/1/2009  
Case Summary  5/1/2009 DONE